GE 531x307ltbajg1 LAN Terminal Board
GE 531x307ltbajg1 LAN Terminal Board
Part Number 531x307ltbajg1 Manufacturer General Electric Country of Manufacture As Per GE Manufacturing Policy Series Mark VI/VIe Function Module Availability In Stock531X307LTBAJG1 is a LAN I/O Terminal Card developed by General Electric. G1 LTB access eight 24 V dc configurable control input plugs. The 8PL connector and input connectors CI1PL through CI8PL are absent from the G2 LTB. Only dc input signals at connector terminals IN1IN8 are compatible with the G2 LTB.
Seven form C relay contact connectors with low voltage, low current, and three terminals each make up the LTB control outputs. The seven high voltage, high current relays are also activated by pilot contact connections. Relay contacts from both boards are accessible when the LTB and RTBA are used together. 531X307LTBAJG1 Functional Description The drive (or exciter) cabinet houses the LAN Terminal Board (LTB). The LTB connects control devices (such as drives) with external devices such as contactors, indicator lights, pushbuttons, and interlocks. There is no adjustable hardware on the LTB. The G1 LTB has eight CI1PL CI8PL 24 V dc programmable control input plugs. These inputs are linked to the 8PL bus, which transports I/O signals between the LTB, the NTB/3TB terminal board, and the drive control board. The LTB has eight input terminal sets for 24 240 V ac or dc input signals.
For usage by the drive control board, the input signals are transformed to 24 V dc logic signals. It should be noted that ac input signals cannot be used on G2 version LTBs. The LTB control outputs are made up of seven low voltage, low current form C relay contact connectors, numbered OT1 through OT7, each with three terminals.
Pilot contact connections are also used to activate the seven high voltage, high current relays. Connector Types The connectors on the LTB are divided into two types: plug-in connectors for ribbon cables and terminal board connectors for individual wires. Plug-in connectors, denoted by the letter PL, provide signal and power I/O within the control device. Terminal board connectors, denoted by the letter TB, link cables from both internal and external devices.
Input Features An input with an ac/dc leakage current higher than 0.5 mA can be made to operate constantly in the ON state by devices connected in series with it. I/O terminal Wiring I/O ribbon cables shouldn't be routed alongside power wires. Capacitive coupling of connection wires in ac applications might result in I/O input leakage (IN1 to IN8). LED Indicators The LTB includes 15 LED indicators that work as follows: LED1 LED8 turn on when the source is applied to circuits IN1 IN8, respectively LED17 LED23 turn on when relays RX1 RX7 turn on, respectivelyUSE 531X307LTBAKG1.
Compatibility
ƒ Compatible with any Series 90-30 CPU except IC693CPU321 and IC693CPU340. Configuration size is limited for CPU311/313/331, as described on the next page.
ƒ Requires release 8.0 CPU firmware. The latest Release 10 is recommended, if available for the particular CPU.
ƒ Requires CIMPLICITY Machine Edition Logic Developer PLC version 3.0 plus the appropriate service pack or special (or a version later than 3.0).
ƒ Not compatible with the VersaPro™, Control, or Logicmaster™ programming software.
ƒ The Series 90-30 Hand-Held Programmer (IC693PRG300) cannot be used to configure this module. New Features The Series 90-30 DeviceNet Master Module allows a Series 90-30 PLC to send and receive I/O data from a DeviceNet network.
Module features include:
ƒ Support for all standard data rates (125K, 250K, 500K)
ƒ Support for 255 bytes input data transfer and 255 bytes output data transfer per slave
ƒ Support for 3972 bytes of input data transfer and 3972 bytes of output data transfer per master
ƒ Support for two I/O connections per Slave - Typically one connection is used for Polled and the other is used for Strobe, Cyclic, or COS
ƒ Support for Poll, Strobe, Cyclic and COS I/O Connections, Fragmented I/O and Explicit Messaging
ƒ Support for Unconnected Message Manager (UCMM) with 1 proxy connection per slave device
ƒ Support for configuration of the global scan rate
ƒ Support for configuration of update rates for Poll and COS/Cyclic on a connection basis
ƒ Support for PLC-application initiated explicit messaging via a COMMREQ
ƒ Master can be configured to operate as a slave simultaneously with master operation
ƒ Configurable fault behavior on loss of communication
ƒ Reports loss or reestablishment of communication with slaves in PLC fault table (configurable)
ƒ Support for 64 network device status bits (note: the bit for the master itself is always zero)
ƒ Firmware update via service port on module