GE DS200TBCAG1A RTD Termination Module
GE DS200TBCAG1A RTD Termination Module
Part Number DS200TBCAG1A Manufacturer General Electric Country of Manufacture As Per GE Manufacturing Policy Series Mark V Function Module Availability In StockDS200TBCAG1A is an RTD Analog Input Terminal Board manufactured by General Electric as part of the Mark V LM Series used in gas turbine control systems. In position nine of the "R5" core, there is the RTD Termination Module (TBCA). On the TBCA terminal board, which is linked to the TCCA board in "R5", are the RTD connections for "R5". The Mark V system is designed to fulfill all gas turbine Control requirements.
The Mark V control boards and control cards part numbers belong to the DS200 series. The Mark V Turbine control system uses digital microprocessors to control the Gas Turbine. The Mark V Speedtronic Control system has a software Implemented Fault Tolerance to increase the reliability of the turbine control system. TBCA CONNECTIONS: JCC - In the "R5" core, writes RTD signals #1 through #15 to the TCCA board. JDD - In the R5> core, writes the RTD signals #16 through #30 to the TCCA board. TBCA HARDWARE CONFIGURATION: The TBCA terminal board does not have any hardware jumpers.
Hardware Tips and Specifications
This DS200TBCAG1A RTD Termination Module, which considered a Mark V Series module product, is not determined to possess any sort of special assembly version outside of its revised status. The GE Analog I/O Terminal Board DS200TBCAG1A features 2 blocks of 90 signal wire terminals and 2 50-pin connectors. One 50-pin connector is labeled JDD and the other is labeled JCC. All of the various hardware elements included in the internal assembly of this DS200TBCAG1A RTD Termination Module should receive some form of protection from this Mark V Series product's normal style of printed circuit board coating, which is a rudimentary base layer of protection applied to the base board and various hardware elements of this DS200TBCAG1A printed circuit board on a functional priority basis.
50-pin connectors are attached to ribbon-type cables that require some special consideration before you connect or disconnect them to prevent damage to the ribbon cable, as introduced in original General Electric instructional manual materials. To disconnect a ribbon cable do not touch the ribbon portion of the cable; hold the connector portion and remove it from the connector on the board, while using your other hand to support the board and keep the board from moving or bending under the pressure. There are potentially multiple signal wires connected to the terminals and so it is best practice to designate where to connect each signal wire by labeling each wire with the ID of the terminal before you disconnect it. With as many as 180 signal wires it is important to eliminate the opportunity for error that would increase the downtime for the drive. Each signal is made up of a few strands of copper wire that might be inadvertently disconnected from the connector. Because of the weight of the drive, and the large number of signal cables, the drive is connected to the board rack through the use of 4 screws. Make sure you utilize all 4 screws during normative installation to support the weight of the board and prevent the board from moving inside the drive.
The Series 90* -30 CPU374 PLUS provides a built-in enhanced Ethernet interface that provides TCP/IP communications with:
▪ Series 90, PACSystems, and VersaMax PLCs
▪ Host computers running the Host Communications Toolkit or CIMPLICITY software
▪ Computers running the TCP/IP version of the programming software CPU Features
▪ High speed Boolean and non-Boolean processing provided by a 586-class 133MHz processor
▪ Two Ethernet ports: 10/100 Mbytes (one IP address) with a built-in, auto-sensing Ethernet switch
▪ Support for EZ Store Device allows you to download a program without a PC
▪ 240KB of user memory Key Ethernet Features
▪ Full PLC programming and configuration services
▪ Periodic data exchange using Ethernet Global Data (EGD) and EGD commands to read and write PLC and EGD exchange memory over the network
▪ TCP/IP communication services using SRTP
▪ Support for SRTP Client (Channels)
▪ Modbus/TCP Server, supporting Modbus Conformance classes 0, 1, and 2.
▪ Modbus/TCP Client, supporting Modbus Conformance classes 0, 1, and Function Codes 15, 22, 23, and 24 for Conformance class 2.
▪ Remote PLC monitoring from a web browser
▪ Comprehensive station management and diagnostic tools
email:1583694102@qq.com
wang@kongjiangauto.com