Bently 3500/92 Communication Gateway
Bently 3500/92 Communication Gateway
OVERVIEW
The 3500/92 Communication Gateway module provides extensive communication capabilities of all rack monitored values and statuses for integration with process control and other automation systems using both Ethernet TCP/IP and serial (RS232/RS422/RS485) communications capabilities. It also permits Ethernet communications with 3500 Rack Configuration Software and Data Acquisition Software. Supported protocols include:
Modicon® Modbus® protocol (via serial communications)
Modbus/TCP protocol (a variant of serial Modbus used for TCP/IP Ethernet communications)
Proprietary Bently Nevada protocol (for communication with 3500 Rack Configuration and Data Acquisition Software packages) The Ethernet connection to the 3500/92 is an RJ45 connection for 10BASE-T star configuration Ethernet networks. The 3500/92 supports the communication interfaces, communication protocols, and other features from the original 3500/90 with the exception of the primary value Modbus registers. The 3500/92 now has a Configurable Modbus Register Utility, which can provide the same functionality originally addressed by the primary value Modbus registers.
Specifications
Power Consumption:5.0 watts typical with ModbusRS232/ RS422 I/O Module
Modbus®::Based on AEG Modicon PI-MBUS300 Reference Manual. Uses Remote Terminal Unit (RTU) transmission mode. Modbus is a registered trademark of Modicon, Inc.
Outputs
Front Panel LEDs
OK LED:Indicates when the 3500/92 is operating properly.
TX/RX LED:Indicates when the 3500/92 is communicating with other modules in the 3500 rack.
Ethernet
Communication Link:Ethernet, 10Mbps, and conforms to IEEE802.3.
Protocol:Ethernet TCP/IP frame and Modbus/TCP.
Connection:RJ-45 (telephone jack style) for 10BASE-T Ethernet cabling.
Environmental Limits Main Module
Operating Temperature:-30 C to +65 C (-22 F to +150 F).
Storage Temperature:40 C to +85 C (-40 F to +185 F).
Humidity:95%, non-condensing.
Key Features and Functions
Wide range of communication capabilities:
The 3500/92 Communication Gateway supports Ethernet TCP/IP and serial (RS232/RS422/RS485) communication protocols, which enables it to communicate with a wide range of devices and systems.
It also supports Ethernet communication with 3500 frame configuration software and data acquisition software, which facilitates remote monitoring and data management.
Multiple protocol support:
Supported protocols include Modicon Modbus (for communication via serial), Modbus/TCP (an alternative form of serial Modbus for TCP/IP Ethernet communication), and Bently Nevada proprietary protocols (for communication with the 3500 Frame configuration and data acquisition software packages).
Configurable Modbus register functionality:
The 3500/92 Communications Gateway has configurable Modbus register functionality, which allows it to provide the same functionality as the initial value registers, increasing the flexibility and customisability of the device.
Status Indication:
LED indicators on the front panel of the device (e.g., OK LED and TX/RX LED) can indicate the device's operating status and communication status, which is convenient for users to carry out troubleshooting and device maintenance.
High Reliability:
The 3500/92 communication gateway adopts high-quality materials and manufacturing process, which can work stably under harsh environmental conditions and ensure long-term operational reliability.