Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

KONGSBERG BWMS system operation and maintenance

F: | Au:FAN | DA:2026-05-12 | 1273 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

KONGSBERG BWMS Bridge Duty Monitoring System: Complete Guide to Installation, Debugging, and Troubleshooting

In modern ship bridge management, ensuring that the bridge is always manned is a key step in preventing accidents such as collisions and grounding. The International Maritime Organization (IMO) has clarified the performance standards for Bridge Navigation Duty Alarm Systems (BNWAS) through MSC. 128 (75) resolution, particularly for vessels operating on a single bridge, which must have reliable activity monitoring and alarm transfer capabilities. The Bridge Watch Monitoring System (BWMS) launched by Kongsberg Maritime is a professional solution that meets this requirement.

However, any electronic system that operates at sea for a long time will face issues such as aging, false alarms, communication interruptions, or configuration errors. For engineers and electronic and electrical personnel, mastering the installation and debugging points, daily operation procedures, and quick troubleshooting methods of BWMS is the core skill to ensure navigation safety and reduce unplanned shutdowns. This article is based on the technical specifications and practical application experience of BWMS, systematically sorting out the complete knowledge system from hardware installation to software configuration, from duty logic to alarm linkage, and providing troubleshooting steps and maintenance suggestions for typical faults.


Overview and Core Functions of BWMS System

2.1 Design Objectives and Compliance

BWMS is an intelligent monitoring system specifically designed to monitor the activity status of bridge personnel. When there is no one on duty on the bridge or the on duty driver loses the ability to operate due to health reasons, the system first emits an audible and visual alarm locally on the bridge. If there is no response, the alarm will be automatically transferred to the captain or other qualified backup navigator. This design fully complies with the technical requirements of IMO MSC. 128 (75) for BNWAS and is applicable to all types of vessels, especially those that have obtained the "one person bridge" classification symbol.

2.2 Main Function List

Central bridge alarm panel: Centralized display of visual and auditory alarms from various navigation devices and systems (such as radar, electronic chart, autopilot).

On duty status monitoring: Automatically detect whether there is personnel operation response in the bridge building based on configurable time intervals. If there is no interaction after the timeout (such as buttons, touch screen clicks, or radar/CDIS operations), the system will determine that there is no one on the bridge or the driver is disabled.

Hierarchical alarm transfer: The first level alarm is triggered locally in the bridge unit; If it is not confirmed or reset within the specified time, the second level alarm will be automatically sent to the captain's cabin or designated location; If there is still no response, further call the backup navigator (such as the first mate or second mate). The transfer path and delay time can be customized.

Manual call for backup navigator: The on duty driver can initiate a call for backup personnel at any time through dedicated buttons on the bridge deck panel without waiting for timeout.


Hardware composition and technical specifications

3.1 Core modules

BWMS adopts a modular design, and the main hardware includes:

Bridge alarm panel: human-machine interaction core, including LCD display, status indicator lights, buzzer, function buttons (system start stop, mute/confirm, timer adjustment, backup call, etc.). The panel supports desktop, ceiling, wall bracket or embedded installation (fixed by hidden screws in corners).

Distributed Processing Unit (DPU):

RDi-32: Input processing unit, used to collect external sensor signals (such as buttons, motion detectors) or alarm contacts from other devices.

RDo-16: Output type processing unit that drives external alarm light bells, relays, or sends signals to the onboard alarm management system.

Midi operation station (MOS-33): a terminal used for system configuration and parameter adjustment, usually placed in the control room or electrical room. Through MOS, advanced operations such as defining the number of navigators, editing alarm description text, and setting alarm grouping logic can be completed.

Power Switching Unit (PSO AD-00479): Automatically switches to the backup DC power supply when the main power supply loses power or fluctuates, ensuring uninterrupted operation of the system.

3.2 Detailed Electrical and Environmental Specifications

Parameter indicators

Supply voltage 18-32 VDC, allowable ± 5% ripple

Typical power consumption 26 W

Working temperature -15 ℃ to+70 ℃

Maximum humidity of 96%, no condensation

EMC compliance IACS E10, IEC 60945 4th edition

The protection level depends on the installation method of the panel, and the front is usually IP22 or higher

3.3 Classification Society Type Certification

BWMS has been recognized by mainstream classification societies worldwide, including DNV, BV, GL (now merged with DNV), RINA, NK, ABS, KR, PRS, MRS (Russian Classification Society), CCS (China Classification Society). This means that the system can be directly installed on any vessel flying any relevant flag without the need for additional testing.


Installation and Wiring Engineering Specification

4.1 Selection of installation locations for bridge alarm panels

It should be installed near the main steering console or navigation workstation, within the range where the duty driver can see and operate with their hands when working normally.

Avoid direct exposure to sunlight, heat source radiation, or direct blowing from air conditioning vents, as this may affect the lifespan of internal circuits or trigger temperature alarms incorrectly.

Sufficient space should be reserved on the back of the panel for wiring and later maintenance; During embedded installation, anti loosening washers should be used for the fixing screws under the four corner decorative cover plate.

4.2 Cabinet layout of distributed processing units

RDi-32, RDo-16 and other DPU units are usually assembled on DIN rails inside the bridge console or in separate junction boxes. Notes:

The communication between DPU and bridge deck panel should use twisted pair shielded cables (recommended Belden 8760 or similar), with a maximum distance of 300 meters.

The dry contact signal line of the input/output terminal should be laid separately from the power cable, with a spacing of at least 200mm, to avoid electromagnetic interference.

Each DPU needs to be assigned a unique address dip switch and registered in MOS-33.

4.3 Power Wiring Requirements

BWMS requires a stable 18-32V DC power supply, and it is recommended to lead a dedicated branch from the 24VDC emergency distribution board and connect it in series with a 5A slow melting fuse. Due to the inclusion of alarm buzzers and relay outputs in the system, the instantaneous starting current can reach 3A, and it is necessary to ensure that the line voltage drop does not exceed 5%. It is recommended to use flame-retardant marine wires with a cross-sectional area of ≥ 1.5mm ². If the ship already has a 24V battery pack, it should be connected through a PSO switching unit to achieve undisturbed conversion between the main/backup power supply.

4.4 Grounding and Shielding

The system's common reference ground should be reliably connected to the ship's main grounding copper bar through M5 bolts. All communication cable shielding layers adopt single ended grounding (only grounded at one end on the bridge deck panel side or DPU side to avoid ground circulation). When not properly grounded, it may manifest as random false alarms or panel display garbled characters.

System settings and parameter configuration

5.1 Initial setting through MOS-33

At the factory, BWMS comes pre installed with the basic firmware of Kongsberg Maritime. The end user needs to complete the specific definitions of the following projects through MOS-33:

Number and level of navigators

In the MOS menu "Crew Setup", enter up to 8 reserve personnel, including Captain, First Officer, Second Officer, etc., and assign priorities (e.g. Level 1 for Captain, Level 2 for First Officer). Each personnel needs to associate an alarm trigger output point (such as a buzzer or information terminal connected to their living quarters).

Alarm description and grouping

The text display of each alarm source can be customized (such as "radar failure", "ECDIS out of step", "autopilot heading deviation") and classified into alarm groups (such as "navigation equipment group", "propulsion monitoring group"). When any alarm is triggered within the same group, the main panel displays it according to the group classification for quick positioning.

Timer parameters

Local Alarm Delay: The time from detecting no one on the bridge to triggering the local sound and light alarm, usually set to 12-30 seconds (IMO recommends no more than 30 seconds).

Master Alarm Delay: The time it takes for a local alarm to be transferred to the captain after it has not been confirmed, usually set to 1-3 minutes.

Third level delay (Backup Alarm Delay): Call the backup navigator after the captain has not responded, recommended for 2-5 minutes.

The above parameters are password protected and can only be modified by authorized electronic electricians or ship captains.

Recovery Mode

Set whether the system automatically clears the alarm sequence and resets the timer when the bridge resumes human activity (such as pressing any confirm button or detecting radar/CDIS operation).

5.2 Tool free on-site debugging

Thanks to the pre programmed architecture, most configurations do not require dedicated debugging software. Engineers only need to follow the "AD-00482 BWM Setup Manual for end user" document provided with the equipment and complete all settings through MOS's wizard interface. If you need to adjust the backlight brightness or buzzer volume of the main panel itself, you can enter it through the hidden menu on the panel (long press 【 Silence 】+【 Acknowledge 】 for 5 seconds).


On duty monitoring logic and operation guide

6.1 On duty detection mechanism

BWMS uses the principle of "activity timeout" to determine whether the bridge building is properly guarded. The system continuously monitors the following two types of events:

Explicit interaction: The on duty driver actively presses the "I'm on watch" button on the bridge deck panel or triggers it through a connected motion sensor (such as an infrared motion detector).

Implicit interaction: Read user input from navigation devices (radar, ECDIS, autopilot) connected to BWMS, such as turning the radar's azimuth knob, changing the display scale of the electronic chart, or adjusting the heading setting of the autopilot. Once any interaction is captured, the internal timer is immediately reset to 0.

When the timer accumulates to the set "first level delay" threshold and no interaction occurs, the system determines to enter the "potential unmanned" state.

6.2 Classification alarm transfer process

Stage 1- Local Reminder: The bridge alarm panel emits a buzzing sound (approximately 85dB) and flashes a red light, while displaying "Bridge Unattended - Please Respond". At this time, the on duty driver should press the 'Acknowledge' button on the dashboard or operate any networked navigation device within 30 seconds. If successful, the timer will reset and everything will return to normal.

Stage 2- Call Captain: After the local reminder timeout, the system automatically triggers the output relay, connects the sound alarm installed in the captain's bedroom/dining room, and sends text to the captain's portable reminder device (if integrated). The captain can respond remotely through a dedicated "takeover" button or rush to the bridge for confirmation. After the response, the system will reset and will no longer continue with the upgrade.

Stage 3- Call the backup navigator: If the captain does not respond within the set time, BWMS activates the third level output and sends an alarm to the residences of the first and second officers until someone responds.

6.3 Manual call backup function

During regular duty hours, if the duty driver needs to temporarily leave the bridge building (such as the restroom or retrieve documents) or feels unwell, they can press the 【 Call Backup 】 button on the dashboard. This will immediately bypass stages 1 and 2 and directly call the backup navigator with the highest priority to come and provide support. This operation is not considered an alarm fault, but it is recorded in the ship safety log.


Common troubleshooting and repair cases

7.1 Fault 1: Frequent false alarms on bridge deck panels (triggered when no one is present)

Phenomenon: Even though VDR playback shows that there is always someone operating the bridge, the system still prompts "Unattended" every few minutes.

Possible reasons:

The installation position of the motion sensor is unreasonable, covering blind spots or being too far away from the main operating position.

Implicit interaction signal not properly connected - radar/CDIS did not send heartbeat or button pulses to BWMS.

If the timer is set too short (e.g. 5 seconds), the driver will be judged as pausing if they do not check the chart normally for a few seconds.

Solution steps:

Check the "Activity Sources" page in MOS-33 to see which interaction device was last detected. If 'None' is displayed, it indicates that BWMS has not received any external input.

Temporarily increase the first level delay of the timer to 45 seconds (for testing purposes) and observe if frequent alarms still occur. If not reported, the original set value is too short and should be set to 15-20 seconds according to the actual working pace.

Check sensor wiring: The infrared motion detector should be installed near the driver's head when seated normally, and avoid the air conditioning outlet (to avoid mistaking airflow for movement). The detector output normally open contact should be connected to the DI terminal of RDi-32.

For integration with radar/ECDIS, it is necessary to ensure that the baud rate of the serial communication between devices (NMEA 0183 or NMEA 2000) matches, and the message format is "$IIACK *". Data can be captured using the "Communication Monitoring" tool within MOS.

7.2 Fault 2: Alarm transfer cannot trigger the captain's cabin alarm

Phenomenon: The local alarm on the bridge tower prompts normally, but after exceeding the time limit, there is no sound or light signal at the captain's location.

Possible reasons:

The output relay (RDo-16 corresponding channel) is damaged or the wiring is loose.

The captain's cabin alarm itself is malfunctioning (such as a burnt buzzer).

The 'Level 1 output' is not correctly associated with a specific physical output point in MOS.

Solution steps:

Enter MOS-33 "Output Test" mode and force the relay of the corresponding port on RDo-16 to be activated. If you can hear the sound of the relay action and measure its contact continuity with a multimeter, then the output board is normal; Otherwise, replace the DPU.

Check if there is any open or short circuit in the cable from the output terminal to the captain's cabin alarm. Measure the control voltage at the alarm terminal (should be 18-32V). If there is no voltage, search for the intermediate junction box.

Reconfigure alarm mapping in MOS: Under the "Alarm Routing" menu, select "Master Level" and check the actual physical output channel number.

7.3 Fault 3: The system cannot power on or intermittently restarts

Phenomenon: The bridge deck panel is black or randomly restarted during normal operation.

Possible reasons:

The DC power supply voltage is lower than 18V (such as being powered by batteries or experiencing excessive voltage drop in the line).

Power Switching Unit (PSO) malfunction, internal relay shaking.

The electrolytic capacitor on the main control board is aging.

Solution steps:

Measure the voltage at the power supply terminals of the bridge deck panel. If it is between 15V and 17V, check if the 24V charger output on board is normal and increase the cross-sectional area of the wire. If the voltage is higher than 32V, it indicates that the voltage regulator has failed, and the power should be immediately disconnected and replaced.

Temporarily bypass the PSO and connect directly to a stable 24V battery pack. If the system is restored to stability, the PSO is faulty. Refer to document AD-00479 to replace the PSO module.

For old batches of equipment, if the capacitor bulges or leaks, contact Kongsberg after-sales for board level repair.

7.4 Fault 4: MOS-33 cannot connect to DPU or bridge panel

Phenomenon: "Comm Error - No Response from Bridge Panel" is displayed on the operation station.

Possible reasons:

Communication cable open circuit or wiring error (A/B wires reversed).

The terminal resistance is not set correctly (in the case of CAN fieldbus).

DPU address conflict.

Solution steps:

Check if the CAN-H and CAN_L wires are correctly connected to all nodes and if the shielding layer is well grounded. The terminal resistor should be connected in parallel with a 120 Ω resistor at each end node of the bus.

Check the dip switch of each DPU to ensure that the address is unique and consistent with the MOS configuration table.

Measure the differential signal voltage using an oscilloscope. During normal idle, CAN-H is about 2.5V to ground and CAN_L is about 2.5V; during communication, the two change in phase. If there is no signal, the main controller is damaged.


Regular maintenance and recommendations for extending lifespan

8.1 Monthly inspection items

Clean the screens and buttons on the bridge deck to prevent poor contact caused by salt spray crystallization.

Test all alarm transfer paths: manually trigger the "unmanned" simulation to confirm that the captain and backup navigator can receive the actual alarm.

Measure the power supply voltage and record it in the engine log. If it drops more than 0.5V compared to the last time, check the circuit or power module.

8.2 Annual Plan

Remove the panel and check for oxidation or looseness in the internal connectors; Apply anti loosening glue to the fasteners.

Use dry compressed air (≤ 3bar) to blow away dust inside the DPU cabinet.

Backup all current configuration parameters to a USB flash drive or laptop through MOS-33 to prevent the need for recovery during device replacement.

8.3 Suggestions for spare parts

According to equipment failure statistics, the following spare parts should be kept on board:

1 bridge deck main control panel (spare part number can be obtained from the label)

2 RDo-16 output DPUs (as relays are vulnerable components)

1 PSO power switching unit

Several 5 × 20mm slow melting fuses (5 each for 2A and 5A)


Differences from the old version of BNWAS and upgrade precautions

Some ships are still using the previous generation BNWAS (which only has a simple timing reset function and no graded alarm transfer or implicit interactive detection). When upgrading to Kongsberg BWMS, please note:

The original alarm light bell can be reused, but it needs to be connected to the RDo-16 output module.

If the original system does not have a motion sensor, it is necessary to install a PIR probe recommended by Kongsberg and adjust the installation angle.

The NMEA interface with the newly installed radar/ECDIS may require a converter (such as RS422 to CAN), it is recommended to contact the original factory to obtain the adapter box.

After completing the upgrade, it is necessary to conduct IMO compliance testing again: simulate driver incapacitation, measure the actual triggering time from timeout to the second level alarm, and ensure that the deviation from the set value does not exceed ± 5%.

  • Rexroth FCS01-1EW0015-A-04 R91131106 Frequency Drive
  • Rexroth MSK050B-0600-NN-M1-UG1-NNN Motor
  • Bosch Indramat TBM1.2-40-W1-115 Bleeder
  • Rexroth HCS01.1E-W0028 Compact Converter
  • Rexroth Indramat MAC071B-0-PS-2-C/095-A-0 Motor
  • Rexroth HCS02.1E-W0012-A-03-NNNN Drive Set
  • Rexroth R-IL S3 BK DI8 DO4-PAC Coupler
  • Rexroth HCS01.1E-W0028-A-03-E-S3-EC-NNN Drive
  • Rexroth MSK061C-0600-NN-S1-UG0-NNNN Motor
  • Bosch Rexroth MSM041B-0300-NN-M0-CH0 Motor
  • Rexroth IKG0071-05.0m Servo Motor Cable
  • Rexroth R-IL S3 BK DI8 DO4-PAC Bus Coupler
  • Bosch Rexroth SB301 Tightening Unit 0608701017
  • Rexroth E-003-S-S Tool Cable 0608740220
  • Rexroth MSM020B-0300-NN-M0-CG0 Servo Motor
  • Rexroth IndraControl VEP30.3 Panel PC
  • Rexroth DBETE-62/315G24K31A1V Valve R901029969
  • Rexroth CSH01.3C-ET-ENS-NNN Control Section
  • Rexroth VT3013-37 Amplifier Control Card
  • Rexroth 1-2 TH6 L 162-10/N 05 Joystick
  • Rexroth ESV025 Handheld Nutrunner 0608841037
  • Rexroth RK2 S30 Amplifier Card VT 4224 U 261
  • Rexroth CDB01.1C-SE-ENS R911308279 Control Unit
  • Rexroth VFC3610-0K40-3P4-MNA-7P Inverter 0.4kW
  • Bosch Indramat HCS02.1E-W0028-A-03-NNNN Servo Module
  • Rexroth DKC01.3-040-7-FW EcoDrive R911279426
  • Rexroth HMV02.1R-W0015-A-07-NNN Utility Unit 15kW
  • Rexroth 0 608 830 193 ZSE220 Communication Module
  • Rexroth VT5003 S41 R5 Proportional Amplifier Card
  • Rexroth KSM02.1B-041c-42N-M1-HP0-ET-L3-D7-NN-FW Motor Drive
  • Mannesmann Rexroth VT5005 S16 R1 Valve Amplifier Card
  • Rexroth CFL01.1-R3 Sercos III Interface Module
  • Rexroth CKK-110-NN-1 Linear Axis with MSK040C
  • Bosch Rexroth 047018-104401 Controller Card
  • Rexroth MDSD1K-2X/4 Solenoid Driver Module
  • Rexroth DKC02.3-012-3-MGP-01VRS Servo Drive
  • Rexroth HCS01.1E-W0006 Compact Servo Drive
  • Rexroth NAM1.2-08 Line Former R911246505
  • Rexroth VPB40 Industrial PC Control Cabinet
  • Rexroth FWA-ECODR3-SGP-03-MS Firmware Module
  • Rexroth HEDE10-31 Pressure Switch R901425475
  • Rexroth HM 17-11/315-C/V0/0 Pressure Sensor
  • Rexroth VFC 3610-2K20-3P4-MNA-7P Inverter 2.2kW
  • Rexroth MSK040C-0600-NN-M1-UG1-NNNN Right Angle Geared Motor
  • Rexroth DKC02.3-012-3-MGP-01VRS EcoDrive Cs
  • Bosch Rexroth MSM031C-0300-NN-M0-CH0 Servo Motor
  • Rexroth HCS02.1E-W0012-A-03-NNNN Power Section
  • Rexroth DBDS 20 P18/400V Pressure Relief Valve
  • Rexroth 3460565500 Pneumatic EP Converter Regulator
  • Rexroth VT-SWA-1-12/DFEE Angle Sensor R900913641
  • Rexroth 0-608-830-250 Interface Module SM24V
  • Rexroth MHD071B-035-NP0-UN8 Servo Motor 12Nm 1000rpm
  • Rexroth MKD025B-144-KG0-KN R911263737 Servo Motor
  • Rexroth KCU02.2N-ET-ET*-025-NN-N-NN-NW Control Unit
  • Rexroth MV-VPB40*3-RB001VPB R911337529 Valve Terminal
  • Bosch Rexroth AS 2/R-2200 Drive Module 3842998041
  • Rexroth HMS01.1N-W0036 Power Section
  • Rexroth CKK-145-NN1 Compact Linear Module
  • Rexroth MS2N04-C0BTN-BSDK0-NNNNN-NN Geared Servo Motor
  • Rexroth HCS02.1E-W0028-A-03-NNNN Power Section
  • Rexroth MS2N04-D0BQN-CMSG0-NNNNN-NN Servo Motor
  • Rexroth MSM031C-0300-NN-M0-CH0 Servo Motor
  • Rexroth MKD041B-144-KP1-KN Servo Motor R911262307
  • Rexroth ESA075G Handheld Nutrunner 0608841033
  • Rexroth MSK070D-0450-NN-M1-UP1-NSNN Motor
  • Rexroth CKK-145-NNG1 Linear Kit with HCS02 Drive
  • Rexroth MSK060C-0300-NN-M1-UG0-NNNN Servo Motor
  • Rexroth MKD090B-047-KP1-KS Servo Motor
  • Rexroth MLS140S-3A-0450-NNN Linear Motor
  • Rexroth VPB40.3 Industrial PC R911338689 CB1
  • Rexroth HCS02.1E-W0012 Servo Drive R911313871
  • Rexroth R151349014 R151145672 Ball Screw Assembly
  • Bosch Rexroth CKK-110-NN-1 Compact Module
  • Rexroth MSK060B-0300-NN-M1-UG1-NNNN Servo Motor
  • Rexroth Indramat TBM 1.2-40-W1-024 Servo Bleeder
  • Rexroth MSK040B-0600-NN-M1-UG1-NNNN Servo Motor
  • Rexroth MLS200S-3A-0450-NNN R911299213 Linear Motor
  • Rexroth SB356 Tool Tightening Controller Rack
  • Rexroth MSK050C-0300-NN-M1-UG0-NNNN Servo Motor
  • Rexroth Indramat DKC11.3-040-7-FW Eco Drive
  • Rexroth VT2000 Proportional Amplifier
  • Rexroth VT1118-10 Analog Module
  • Rexroth MSK060C-0600-NN-M1-UP1-NSNN Motor
  • Rexroth MSK060C-0300-NN-S1-UG0-NNNN Motor
  • Rexroth R911173937 IndraControl XM AI1
  • Rexroth R412018225 AES-D-BC-ECAT Module
  • Rexroth CDB02.1B R911338542 Controller Card
  • Rexroth VT-HNC100-2-30/P-I-00/000 Module
  • Bosch Rexroth CSB02.1B R911372549 Control
  • Bosch Rexroth R185321310 Runner Block
  • Rexroth VPB40.3 Industrial PC R911338689
  • Rexroth HNK01.1A-A075-E0106-A-500 Drive Controller
  • Rexroth CSH02.1B-CC-EC-ET-S4-NN-NN-FW Controller
  • Rexroth CSB01.1C-PB-ENS-NNN Control Unit
  • Rexroth MKD041B-144-KP0-KN Permanent Magnet Motor
  • Rexroth SE-B2.020.030-14.000 Servo Motor
  • Rexroth MSK060C-0600-NN-M1-UG0-NNNN Servo Motor
  • Rexroth HCS01.1E-W0018-A-03-B Drive Controller
  • Rexroth 3 842 547 996 IE3 Geared Motor
  • Rexroth CSH01.1C-NN-ENS R911309709 Control Section
  • Rexroth R151349013 Ball Screw Nut
  • Mannesmann Rexroth VT3006-36 Analog Amplifier Card
  • Bosch Rexroth R900086160 PGF1 Gear Pump
  • Bosch Rexroth R911173263 VDP15.3 Touch Display
  • Bosch Rexroth PPC-R22.1 RJ522 Industrial Controller
  • Bosch Rexroth MSK060C-0300-NN-S1-UG0-NNNN Servo Motor
  • Bosch Rexroth R911325068 NYS04.1 Controller
  • Bosch Rexroth R911335439 CSH01.1C Control Unit
  • Bosch Rexroth R917010287 BODAS RC10 Controller
  • Bosch Rexroth R911329791 CSH01.1C Drive Controller
  • Bosch Rexroth R182432310 Runner Block Guide
  • Bosch Rexroth VT-VSPA2-1-11 Amplifier Card R900021909
  • Bosch Rexroth MKD090B-047-KG1-KN Servo Motor
  • Bosch Rexroth LTU350 Servo Amplifier 0608750108
  • Bosch Rexroth 5610102050 Pneumatic Vacuum Regulator
  • Bosch Rexroth VT5041-23/3-OV PLC Control Board
  • Bosch Rexroth VT3015 S10/E Servo Amplifier Board
  • Bosch Rexroth MSK070D-0300-NN-M2-UG1 Servo Motor
  • Bosch Rexroth 3DREP6C-21 Valve R900955887
  • Bosch Rexroth R151244013 Ball Screw Bearing Unit
  • Bosch Rexroth MSM031C-0300 Servomotor R911325140
  • Bosch Rexroth EMD-B16.1-DC024N Box R911291681
  • Bosch Rexroth MKD071B-061-GP0-KN Servo Motor
  • Bosch Rexroth MSK030C-0900-NN-M1-UG1 Servo Motor
  • Bosch Rexroth EcoDrive DKC01.3-004-3-MGP-01 Servo Controller (299772)
  • Bosch Rexroth DKC02.3-040-7 EcoDrive Controller
  • Bosch Rexroth CLC-D02.3 CLC Motion Control Board
  • Bosch Rexroth HDS05.2-W300N Drive R911190019