2cross section). An insulated
external 5mm (0.2in) jumper such as Altech #8879 can be used to connect adjacent points. When
an external jumper is used, the wire capacity is reduced from AWG #14 (2.10mm
2) to AWG #16
(1.32mm
2Wire to Board Connectors
The I/O Terminal Block with Connectors (catalog number IC670CHS003 and 103) has two 20-pin
male connectors for I/O wiring. The mating connector is Amp part number 178289-8. The
connectors are keyed to prevent wrong insertion. Any tin-plated contact in the AMP D-3000 series
can be used with the connector (Amp part number 1-175217-5 for high contact force receptacle for
20-24 gauge (0.20-0.56mm
2wires), 1-175218-5 for high contact force receptacle for 16-20 gauge
(0.56-1.42mm
2)
). A kit containing two mating connector housings and contacts is available as GE
Fanuc part number IC670ACC003. The kit contains pins for 16-20 gauge wire. A crimping tool is
not provided in this kit.
Thermocouple Terminal Block
The Thermocouple Terminal Block (IC670CHS004), which has two built-in thermistors, can be
used to provide local reference junction compensation for thermocouples used in conjunction with
Field Control Thermocouple modules.
Thermocouples are connected to the screw terminals on the Thermocouple Terminal Block.
Thermocouple modules are installed on a separate I/O Terminal Block (IC670CHS003, -002, or
-001) and connected to Wire-to-Board connectors on the Thermocouple Terminal Block. Terminal
Block IC670CHS003 provides connector to connector installation