Housing
Pos: 11.18 /Technische Daten / Datenblatt/Aktorik/Stellungsregler/TZIDC / TZIDC-200/Technische Daten/Gehäuse TZIDC @ 10mod_1176272981281_3101.doc @ 78062
Material/Protections
Aluminum, protection class IP 65 / NEMA 4X
Surface/color
Electrostatic dipping varnish with epoxy resin, stove-hardened. Case
varnished black, RAL 9005, matte, housing cover Pantone 420.
Electrical connections
Screw terminals: Max. 1.0 mm2 for options,
Max. 2.5 mm2 for analog signal.
Note: Do not expose the terminals to strain.
Cable entry: 2 tap holes 1/2-14 NPT or
M20 x 1.5 (1 x with cable gland and
1 x with pipe plug)
Pneumatic connections
Threads G 1/4 or 1/4-18 NPT
Weight
1.7 kg (3.75 lb)
Mounting orientation
any orientation allowed
Dimensions
see dimensional drawings
ATEX II 3G EEx n A II T6
Prototype test certificate: TÜV 02 ATEX 1943 X
Type: Explosion-proof equipment
(Zone 2)
Device class: II 3G (EEx n A II)
Temperature class: T4, T5, T6
Permissible ambient temperature: T4: -40 °C ≤ Tamb ≤ 85 °C
T5: -40 °C ≤ Tamb ≤ 65 °C
T6: -40 °C ≤ Tamb ≤ 50 °C
ATEX II 2 D IP 6X T 46 °C
Prototype test certificate: TÜV 04 ATEX 2702 X
Type: Intrinsically safe equipment
Device class: II 2 D (IP 6X)
IECEx Ex ib IIC T6
Prototype test certificate: IECEx TUN 04.0015X,
Issue no.: 0
Type: Intrinsically safe
Temperature class: T4, T5, T6
Permissible ambient temperature: T4: -40 °C ≤ Tamb ≤ 85 °C
T5: -40 °C ≤ Tamb ≤ 50 °C
T6: -40 °C ≤ Tamb ≤ 35 °C
email:1583694102@qq.com