Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Yaskawa ∑ - II Servo Drive Debugging Guide

F: | Au:FAN | DA:2026-04-22 | 540 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Yaskawa ∑ - II Series SGMBH/SGDH Servo Drivers: A Complete Technical Manual from Installation to Advanced Debugging

In the fields of high-end mechanical manufacturing, large-scale automated production lines, and precision positioning control, 400V level high-power servo systems play a core driving role. The combination of SGMBH servo motors (22-55 kW) and SGDH servo drives (SERVOPACK) in the Yaskawa ∑ - II series is widely used in presses, injection molding machines, large gantry machines, and wind pitch systems due to its high response, high precision, and rich control modes (speed, position, torque). This article is based on the original factory technical manual and provides a comprehensive operation guide for on-site engineers, system integrators, and maintenance personnel, covering hardware installation, main circuit wiring, parameter initialization, trial operation, gain adjustment, and fault diagnosis.


Chapter 1: Product Overview and Acceptance Inspection

1.1 System composition

The ∑ - II series 400V servo drive system consists of SGMBH servo motors (synchronous type, rated speed of 1500 min ⁻¹, maximum speed of 2000 min ⁻¹, maximum torque of 200%) and SGDH SERVOPACK (speed/torque/position control optional). The motor is equipped with a 17 bit incremental or absolute encoder (optional 20 bit absolute).

1.2 Open box inspection

After receiving the product, it is necessary to confirm:

Does the servo motor match the SERVOPACK model (see manual combination specification table, such as SGDH-2BD with SGDH-2BE).

Can the motor shaft be smoothly rotated manually (motors with brakes cannot be manually rotated).

Check for any transportation damage to the appearance and loose screws.

Check the nameplate data: voltage level (400V level), rated current, serial number, etc.

1.3 Storage Environment

Servo motor: -20~60 ℃.

SERVOPACK: -20~85 ℃.

Humidity: below 90% RH (no condensation).


Chapter 2: Installation and Mechanical Connection - Ensuring Long term Reliable Operation

2.1 Installation of servo motor

SGMBH motors can be installed horizontally or vertically. Before installation, it is necessary to remove the anti rust coating on the shaft end with diluent (to avoid contact with other parts). The installation surface must meet the following requirements:

Concentricity: The concentricity between the flange mating surface and the output shaft is T.I.R. ≤ 0.05 mm.

Verticality: The verticality T.I.R. between the flange surface and the output shaft is ≤ 0.05 mm.

Shaft runout: Shaft end runout T.I.R. ≤ 0.03 mm.

2.2 Allowable radial/axial loads

When designing a mechanical system, the radial load (Fr) and axial load (Fs) borne by the shaft end shall not exceed the following table:

Motor model allows radial load Fr (N) and axial load Fs (N), with a distance of LR (mm) from the point of application

SGMBH-2BD 5880 2156 100

SGMBH-3ZD 6272 2156 100

SGMBH-3GD 7448 2156 100

SGMBH-4ED 7840 2156 100

SGMBH-5ED 8428 2156 110

Important: Exceeding the allowable load can cause bearing damage or encoder failure. It is strictly prohibited to directly impact the shaft end when installing the coupling.

2.3 Motor fan and thermal protection

The SGMBH motor comes with a fan, which needs to be connected to a three-phase 380-480V power supply (terminals U (A), V (B), W (C)), and ensure that the wind direction is correct (switch the two phases arbitrarily when reversing). The fan is equipped with a built-in thermal protector (operating temperature 140 ℃± 5%), which needs to be used in conjunction with a 2A non fuse circuit breaker. The internal thermostat of the motor (terminals 1 and 1b) must be connected to the control circuit, and the main power or servo must be cut off when the thermostat is activated.

2.4 SERVOPACK Installation

SGDH is a base mounted type that must be installed vertically and meet the following spacing requirements:

At least 50 mm up and down, and at least 10 mm left and right.

The ambient temperature is 0-55 ℃, the humidity is ≤ 90% RH, and the vibration is ≤ 4.9 m/s ².

When multiple units are installed side by side, a cooling fan needs to be installed at the top to ensure that the temperature inside the cabinet does not exceed 45 ℃ (long-term reliability).

2.5 Power loss reference

SERVOPACK model main circuit loss (W) control circuit loss (W) total loss (W)

SGDH-2BDE 650 120 770

SGDH-3ZDE 880 170 1090

SGDH-3GDE 1050 140 1260

SGDH-4EDE 1350 150 1560

SGDH-5EDE 1600 180 1840

Chapter 3: Wiring of Main Circuit and Control Circuit - Safety and Anti Interference

3.1 Definition of main circuit terminals

Terminal symbol function description

L1/R, L2/S, L3/T main power input three-phase 380~480VAC ± 10%, 50/60Hz

U. V, W motors are connected to servo motors U, V, W

DC24P, DC24N control power input 24VDC ± 15%

+1. Connect the+2 DC reactor to the factory short-circuit for harmonic suppression

B1 and B2 regenerative resistors are connected to external regenerative resistor units

DU, DV, DW dynamic braking unit connection for models of 37kW and above

DBON, DB24 dynamic braking unit controls models of 37kW and above

3.2 Typical Wiring Example (22/30kW)

The main power supply is connected to L1/L2/L3 through MCCB (recommended 100-150A) and electromagnetic contactor (MC).

The control power supply DC24V needs to be provided by the user (SELV, double insulation) and connected to DC24P/DC24N.

The motor power line (U/V/W) must be routed separately from the encoder cable (with a spacing of ≥ 30cm), using shielded twisted pair cables.

Grounding: 400V level grounding resistance ≤ 10 Ω, must be dedicated to grounding, and cannot share grounding electrodes with high current equipment such as welding machines.

3.3 Control circuit I/O signal (CN1 50 pin)

The key signals are as follows:

Input signal (optocoupler isolation, requires external 24V power supply)

/S-ON (CN1-40): Servo ON (low level effective)

/P-CON (CN1-41): Proportional Control Reference/Control Mode Switching/Zero Position Clamping

P-OT (CN1-42): Forward overtravel prohibited (high-level prohibits forward operation)

N-OT (CN1-43): Reverse overtravel prohibited

/ALM-RST (CN1-44): Alarm reset

/P-CL (CN1-45): Positive torque limit/internal speed selection

/N-CL (CN1-46): Reverse torque limit/internal speed selection

+24VIN (CN1-47): External 24V input

Output signal (optocoupler/open collector)

ALM+/ALM - (31/32): Servo alarm (open circuit when alarm)

/TGON+/TGON - (27/28): Rotation detection (conducts when the motor speed exceeds the set value)

/S-RDY+/S-RDY - (29/30): Servo ready

PAO/PBO/PCO: Encoder divided output (A/B/C phase, line driven)

ALO1/2/3 (37/38/39): Alarm code output (open collector)

/V-CMP (25/26): Consistent speed/positioning completed

3.4 Precautions for Interface Circuit

Analog input (V-REF speed reference, T-REF torque reference): Input impedance of approximately 14k Ω, maximum ± 12V. Use shielded twisted pair cables.

Pulse input (PULS, SIGN): Supports line drive (5V) or open collector (5V/12V), with a maximum frequency of 500kpps (line drive). When using the built-in 12V pull-up power supply, the input resistor should limit the current to 7-15mA.

Encoder interface (CN2): Use a dedicated cable (up to 20m in length, up to 50m in special specifications), with a shielding layer grounded at one end.


Chapter 4: Trial Operation - Two Step Verification without Load and with Load

4.1 Safety Notice

The first trial run must disconnect the coupling between the motor and the machinery, and only test the motor without load.

Confirm that all wiring is correct, especially that the main power supply is not mistakenly connected to U/V/W.

Confirm that the P-OT/N-OT signal is valid (low level allows operation, high level prohibits), otherwise the motor may not start.

4.2 Steps for no-load trial operation

Power on: Connect the control power supply (DC24V) and the main power supply (three-phase 400V). The SERVOPACK panel LED displays "-" (standby). If an alarm code (such as A.10, A.30, etc.) is displayed, there may be a wiring or hardware malfunction.

Using the digital manipulator (JUSP-OP02A-2):

Connect the operator to CN3 (electrically pluggable).

Press the DSPL/SET key to enter the auxiliary function mode (Fn002).

Press DATA/ENTER, then press SVON to enable the servo (the panel displays "run").

Press the UP or DOWN key, and the motor rotates at a jog speed (Pn304 defaults to 500 min ⁻¹).

Check rotation direction: The default forward direction is counterclockwise (CCW) when viewed from the load side. If reversed, the parameter Pn000.0 can be changed (set to 1 reverse direction), or the motor U/V/W phases can be exchanged.

Run with external reference (speed control):

Set parameter Pn000.1=0 (speed control).

CN1-5 (V-REF) input 0~± 10V, the motor speed should be proportional to the input voltage (default 6V corresponds to rated speed of 1500 min ⁻¹).

View the actual speed through monitoring mode (Un000) and adjust Pn300 (speed reference input gain) to ensure the correct voltage speed relationship.

4.3 Load Test Run

After passing the no-load test, connect the mechanical load and perform self-tuning. Use the auxiliary function Fn001 to set the mechanical rigidity level (1-10). The higher the level, the faster the response, but it may cause vibration. Usually starting from 4, gradually increasing until vibration occurs and then decreasing by one level. Enable online self-tuning (Pn110.0=1), SERVOPACK will automatically calculate the load inertia ratio (Pn103) and optimize the speed loop gain (Pn100) and position loop gain (Pn102).

Chapter 5: Detailed Explanation of Parameters and Application Functions

5.1 Classification of Basic Parameters

Main functions of category parameter range

Function selection: Pn000~Pn003 control mode, rotation direction, stop mode, alarm code output, etc

Gain related Pn100~Pn123 speed loop gain, integration time, position loop gain, inertia ratio, feedforward, etc

Position control Pn200~Pn208 pulse input form, electronic gear, filter

Speed control Pn300~Pn308 speed reference gain, internal speed 1-3, soft start time, jog speed

Torque control Pn400~Pn409 torque reference gain, torque limit, notch filter

Sequence related Pn500~Pn512 positioning completion width, zero speed clamp level, brake output timing, I/O allocation

5.2 Examples of Key Parameter Settings

Control mode selection (Pn000.1)

Set value control mode

0 speed control (simulation reference)

Position control (pulse reference)

2 Torque Control (Simulation Reference)

3-contact input speed control (internal speed)

7-position control ↔  Speed control (via/P-CON switching)

9 Torque Control ↔  speed control

Electronic gear settings (Pn202/Pn203) - position control is required

Electronic gear ratio B/A=(number of encoder pulses x 4)/(reference unit per revolution of load shaft) x (motor speed/load shaft speed)

For example: 17 bit encoder (32768 pulses/rev), screw pitch 5mm, reference unit 0.001mm, direct connection (reduction ratio 1:1):

Reference unit per revolution of load axis=5/0.001=5000

Electronic gear ratio=(32768 × 4)/5000=131072/5000=26.2144 → rounded to approximately 262144/10000 (needs to be simplified to integer ≤ 65535). Actual setting: Pn202=262144/4? Careful calculation is required. The manual provides examples: Pn202=8192, Pn203=6000.

Speed reference input gain (Pn300) - speed control

The factory value is 600, which corresponds to the rated speed of 6V (1500 min ⁻¹). If 10V corresponds to 1500 min ⁻¹, then Pn300=1000 (10V/1500 min ⁻¹, every 0.01V corresponds to 1 min ⁻¹).

Torque reference input gain (Pn400) - torque control

The factory value is 30, which corresponds to a rated torque of 3V (100%). If 10V is required to correspond to the rated torque, Pn400=100.

5.3 Advanced Features

Full range automatic torque boost: No need to set, SERVOPACK automatically adjusts the output voltage according to the load.

Speed feedback compensation (Pn111): used to shorten the positioning and setting time, usually used in conjunction with self-tuning.

Mode Switch (Pn10B. 0): It can automatically switch PI/P control based on torque, speed, acceleration, or position error to suppress overshoot.

Notch filter (Pn408.0, Pn409): When resonance (sharp noise) occurs in the mechanical system, setting the frequency of the notch filter (50~2000Hz) can eliminate vibration.

Zero Clamp (Pn000.1=A): When the speed reference is lower than the set level (Pn501) and the/P-CON signal is ON, the servo automatically locks in the zero position.

Holding Brake Control: Vertical axis applications require the use of a brake motor. Set the brake output timing for parameters Pn506~Pn508 to prevent gravitational sliding.


Chapter 6: Deep Application of Digital Operator (JUSP-OP02A-2)

6.1 Basic Operations

Status display mode: default display after power on, can view I/O status (indicated by 8 LEDs).

Parameter setting mode: Press the DSPL/SET key to switch to the "Pn" display, select the parameter number, press DATA/ENTER to read, and after modification, press DATA/ENTER to save (the panel will flash). Function selection parameters (such as Pn000) need to be modified bit by bit.

Monitoring mode: Display Un000~Un00D, including actual speed, reference speed, torque, position error, I/O status, etc.

6.2 Auxiliary Functions (Fn000~Fn014)

Function code usage

Fn000 alarm traceability display (last 10 alarms)

Fn001 mechanical rigidity setting (for self-tuning)

Fn002 jog operation

Fn003 Zero Point Search

Fn005 parameter initialization (factory reset)

Fn006 Clears Alarm Traceability Data

Fn007 saves self-tuning results (inertia ratio written to EEPROM)

Fn008 absolute value encoder multi cycle reset

Fn009 automatic adjustment simulation reference zero drift

Fn00A/Fn00B manual adjustment speed/torque reference zero drift

Fn010 password setting (to prevent parameter errors)

Fn013 multi turn limit setting (absolute value encoder)

6.3 Zero drift adjustment

When the speed reference is 0V, the motor still rotates slowly and needs to adjust the zero drift. Prioritize using Fn009 automatic adjustment (input 0V reference in servo OFF state). If the position ring is formed on the host side, use manual adjustment (Fn00A, adjustment value range -9999~+9999).

Chapter 7: Fault Diagnosis and Alarm Handling

7.1 Common Alarm Codes and Countermeasures

Display alarm name, common causes, and handling measures

A. 02 Parameter damage: Power off when writing parameters, execute Fn005 initialization, and reset

A. 10. Check U/V/W insulation for overcurrent or overheating of radiator motor wires, grounding, excessive load, and fan faults; Reduce load; Check the fan and heat dissipation

A. 30. Abnormal regeneration transistor fault and broken regeneration resistor. Check the external regeneration resistor wiring; Replace SERVOPACK

A. 32 regeneration overload regeneration energy exceeds the capacity of the resistor, external larger power regeneration resistor is connected, set Pn600

A. Check the input voltage for overvoltage, high power supply voltage, and rapid deceleration in the 40 main circuit; Extend deceleration time; Install regenerative resistor

A. 41. Check the power supply and wiring for undervoltage, phase loss, and fuse burnout in the main circuit; Replace SERVOPACK

A. Check the U/V/W wiring for phase sequence error and excessive reference input of the 51 overspeed motor line; Reduce reference value

A. 71/72 overload (high/low load) with excessive load and reduced load due to broken motor wires; Check the motor power line

A. 81 Absolute value encoder backup error battery voltage depletion, encoder+5V loss, battery replacement; Perform Fn008 initialization

A. 83 Absolute Value Encoder Battery Error Battery voltage<2.7V Replace battery when powered on (ER6VC3 or JZSP-BA01)

A. CC multi cycle limit inconsistency SERVPCACK and encoder multi cycle setting are different. After modifying Pn205, execute Fn013

A. The d0 position error pulse overflow position gain is too low, the load inertia is large, and the pulse frequency is too high, increasing Pn102; Reduce the electronic gear ratio; Check the machinery

A. F1 power supply phase loss inspection, main power supply phase loss inspection, L1/L2/L3 wiring and MCCB

7.2 Alarm Reset

Press the RESET button on the numeric operator (while pressing UP+DOWN on the panel operator).

Through the CN1-44 (/ALM-RST) signal (low level active).

Partial alarms (A.02, A.04, A.81, A.82, etc.) require power outage and restart.

7.3 Troubleshooting of motor not rotating despite no alarm display

Check if/S-ON is at low level (servo enabled).

Check if P-OT/N-OT is at low level (operation is prohibited when overtravel is prohibited).

Check if the control power supply DC24V is normal.

Speed control mode: Check if there is voltage in V-REF; Position control mode: Check if PULS signal is input.

When using an absolute value encoder, the SEN signal must be at a high level (absolute data request).


Chapter 8: Maintenance and upkeep

8.1 Regular inspection items

Component cycle inspection content

Daily vibration, abnormal noise, and surface cleaning of the motor

The insulation resistance of the motor is measured annually with a 500V megohmmeter, and is ≥ 10M Ω (with SERVOPACK disconnected)

Oil seal replaced every 5000 hours

SERVOPACK cooling fan replacement in 4-5 years

Smooth capacitors should be checked for leakage and discoloration after 7-8 years, and replaced if necessary

Circuit board electrolytic capacitor 5-year test, replace circuit board if necessary

8.2 Absolute value encoder battery replacement

When an A.83 alarm occurs, the battery (model ER6VC3 or JZSP-BA01) must be replaced while the SERVOPACK control power supply is powered on. After replacement, turn off the power and then turn it back on to clear the alarm. If the battery is completely discharged and multiple cycles of data are lost, Fn008 needs to be executed to reset multiple cycles of data and reset the zero point.

8.3 Precautions for long-term discontinuation

If stored for a long time (more than 6 months), it is recommended to power on every six months to prevent the degradation of electrolytic capacitors.


Chapter 9: Selection and Combination Quick Search

9.1 Combination Table of Servo Motor and SERVOPACK

Rated power of servo motor SERVOPACK Continuous current (A) Maximum current (A) Allowable load inertia (× 10 ⁻⁴ kg · m ²)

SGMBH-2BD 22kW SGDH-2BDE 58 120 2960

SGMBH-3ZD 30kW SGDH-3ZDE 80 170 3865

SGMBH-3GD 37kW SGDH-3GDE 100 210 6950

SGMBH-4ED 45kW SGDH-4EDE 127 260 7550

SGMBH-5ED 55kW SGDH-5EDE 150 310 9850

9.2 External Regenerative Resistance Unit

SERVOPACK regeneration resistor unit resistance value (Ω) capacity (W)

2BDE/3ZDE JUSP-RA12 9 3600

3GDE JUSP-RA14 5 4800

4EDE JUSP-RA15 4 6000

5EDE JUSP-RA16 3.8 7200

9.3 Recommended MCCB and noise filter

SERVOPACK MCCB Capacity (A) Recommended Noise Filter

2BDE 100 FN258L-75-34

3ZDE/3GDE 150 FN258L-100-35 / FN258L-130-35

4EDE/5EDE 225 FN258L-180-07

  • Atlas Copco PF3000-C-HW Tensor S4 S7 RBU Controller
  • Atlas Copco PPBE0613 24VAC Control Panel
  • Atlas Copco PF3000-C-HW Tensor S4 S7 Controller
  • Atlas Copco Neos ARC-D130-S+ Inverter Drive
  • Atlas Copco Power Focus SL PF4002-G-HW Controller
  • Atlas Copco 8436 6770 00 ILT Base Station
  • Atlas Copco 1900520400 Air Compressor Control Panel
  • Atlas Copco 1900-0711-51 Display Keypad Unit
  • Atlas Copco 1900-0710-52 Communication Control Board
  • Atlas Copco 1900-0701-04 Control Interface Module
  • Atlas Copco 8092 1143 40 SRTT Transducer 180Nm
  • Atlas Copco MT Focus 6000 Controller with Pump and Screwdriver
  • Atlas Copco Elektronikon GraphicPlus Controller PPBE0622 PPBE0633
  • Atlas Copco PF3109-G-DN-HW Tensor 8-9 Power Focus Nutrunner Control
  • Atlas Copco Elektronikon P1900520440 Touch Controller
  • Atlas Copco Power Focus 8 Controller 8436280002
  • Atlas Copco 8436 1500 03 FlexCarrier 3-Slot Torque System Component
  • Atlas Copco Power Focus 6000 PF6000 Industrial Controller
  • Atlas Copco TC-4000-P-PB-ES Power Macs Controller
  • Atlas Copco 8433-0015-20 8433001520 Cable Assembly
  • Atlas Copco 49X10301AB Pressure Transducer Sensor
  • Atlas Copco 8436180002 Replacement Filter Element
  • Atlas Copco C4700A01V216 Compressor Control Module
  • Alcatel-Lucent 3HE01019AAAA01 High-Speed Interface Module
  • Alcatel-Lucent 111381 Power Distribution Module
  • Alcatel TN 2523 1:1 CDN III Module – MRPQAE3
  • Alcatel-Lucent 3he06151aaac01 8-Port Interface Module – IPUIBKB3AA
  • Alcatel-Lucent LNW46 DMX Metro OC12 Interface Module – 108694878
  • Alcatel-Lucent 41A12C FT-2000 Optical Transponder Unit – 108188053
  • Alcatel-Lucent 8DG02607AA POW100 DC-DC Converter Module
  • Alcatel-Lucent LambdaXtreme WWBQ21 40G Optical Transponder
  • Alcatel-Lucent TN1891 5ESS Protocol Handler PHV5 Commcode 108747064
  • Alcatel-Lucent 300-0303-900 T1D3PDL1AE Digital Matrix Card
  • Alcatel-Lucent G-821M-A Module
  • Alcatel Lucent MPT-GC Eth 1G+ARM TX 81-86GHz 3DB80005AAAAO1
  • Nokia 3KC48990AB 1830PSS 16FAN2 Fan Unit
  • Alcatel 3EC17041AA PSPC-G4 PCB CP011200552
  • Alcatel 300-0437-906 Rev F DEXCS DMC T1D1L0S Module
  • Alcatel-Lucent 3DW03697ABBA01 TFD64A Module
  • Alcatel-Lucent AWR12 S1-1 UN Interface T3PQAC3AAA
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC 3DB20914BAAA03 6GHZ
  • Alcatel-Lucent 9500-MPR ODU 300 11GHz Microwave Radio MPT 3DB23035AEAA01
  • Alcatel 2C7-1005-000 Teflon Bell Jar Holder Ring – 146111
  • Alcatel-Lucent BNJ118 S1:4 Circuit Board – Interface Module
  • Alcatel-Lucent 9500-MPR ODU 300 6GHz Microwave Radio MPT 3DB23215AFAA01
  • Alcatel 3EM04001AA Signal Processing Unit with Accessory Cards
  • Alcatel VAUCAL5KAB AA1418FE2BG 3FE67437AAD02 Interface Card
  • Alcatel-Lucent 1642 Edge Multiplexer N1217P YF – Access Node
  • Alcatel-Lucent 3HE07158BA 7750 SR-12 12-Port 10GIGE MultiCore IMM IPUCA741AA
  • Alcatel 101200429000 Power Divider 746-776 MHz with Heatsinks
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ADAA01 High Power Radio
  • Alcatel-Lucent 9500-MPR MPT-HC 23GHz 2/2P ODU Radio 3DB20474BA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215AAAA01 Low Power Radio
  • Alcatel 3BA52126ABAA OmniPCX 4400 Compact Cabinet
  • Alcatel-Lucent 3HE12300AA 7750 SR-1 Subrack with Licenses
  • Alcatel 300-1368-903 Rev C DEXCS SPA-1 T1PQAC1 Line Card
  • Alcatel-Lucent 408977981 WOWUAB6HAA 10G XPR OTU2 XPonder Card
  • Alcatel-Lucent-Nokia 3HE08423AARC01 7750 SR Control Processor Module IPUCBGZ1AA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ABAA01 Low Power Radio
  • Alcatel-Lucent CPU7-2 3BA23259ABJE 05 Control Processor Module
  • Alcatel WTM11AD 3DW03915DABA01 Optical Transponder Module
  • Alcatel-Lucent 1340FMPK Card Chip BA5IVY6BAA – Processor Module
  • Alcatel-Lucent 3HE06151ACAC01 Control Fabric Module
  • Alcatel-Lucent 9500-MPR 18GHz 1P-1 Protection ODU Radio 3DB20433BA AA04
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 18GHz Radio 3DB20433BAAA04
  • Alcatel-Lucent SM269 LMPQ04KAXX Circuit Pack – Interface Module
  • Alcatel OME25HP Filter Cartridge – 107494
  • Alcatel-Lucent ALU-BZ74 99BC-4 –48V Battery Cabinet
  • Alcatel-Lucent WWAA37 Optical Amplifier WMAPZNZAAB – CP Series
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC MPT-XP 3DB20476BAAA04 23GHZ
  • Alcatel Tyco Yukon ES760A Rectifier
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 23GHz 3DB23045HMAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 11GHz 3DB20548ACAA01 Microwave Radio
  • Alcatel Lucent 3DH03173AKAA Module
  • Alcatel-Lucent 76-0300-02 CSM-V2 PCB
  • Alcatel 9400 UX ODU Module 3CC06729ABAA
  • Alcatel-Lucent 408981363 Jigsaw A Band Block 24/-48V KS24624L58
  • Alcatel 3BA53095 PCB Card
  • Alcatel 2C7-1005-000 Bell Jar Holder Ring Teflon PC7-1005-000
  • Alcatel-Lucent ES640 PWDQAGKUAA 5ESS 48V DC Alarm Control Unit
  • Alcatel-Lucent 9500-MPR ODU 300 23GHz Microwave Radio MPT 3DB23045HM
  • Alcatel-Lucent KFA720 WMOTCMVLAB Optical System Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 15GHz Microwave Radio 3DB20373BAAB04
  • Alcatel-Lucent AKM70 S1-7 SMUX1 Sub-Multiplexer – T3PQWAEAAH
  • Alcatel-Lucent 107486490 DDM-2000 SONET DS3 Circuit Pack – BBG4B
  • Alcatel-Lucent SBEVM BNJ82 1:12 Module – AV950-01168
  • Alcatel-Lucent 938A Optical Loss Set – Test & Measurement Kit
  • Alcatel-Lucent MS1025-25O16-ED Fiber Optic Unit – 48VDC
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 1/1P Microwave Radio 3DB20473BA AA04
  • Alcatel-Lucent bCEM-U Control Module – 3BK28676ABAC01
  • Alcatel ASI20 Detector Control Module
  • Alcatel Lucent 130B S-1 PWPQ08B Power Unit
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20441BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20824AAAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20822AAAB02 Microwave Radio
  • Alcatel-Lucent 3AL92111AA 1P10GSO Interface Module
  • Alcatel 8220 CTT 450 Turbo Pump Controller 127821
  • Alcatel-Lucent 3AL78823AAAE 02 Module
  • Alcatel-Lucent 90-0413-01 Universal Card
  • Alcatel-Lucent BRMA 10Base-T/100Base-TX Connecting Box 3BA56170ACAB010842
  • Woodward Micronet 5453-279 Rev E Chassis Rack for TMR Control
  • Alcatel-Lucent KFA632 WMOTBUKLAA 10G Optical Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 3DB20474BAAB04 23GHz Microwave Radio
  • Alcatel-Lucent KFA720 WMOTCMVLAB SFP/XFP Optical Interface Carrier
  • Alcatel-Lucent 3AL00114AB Universal Interface Module
  • Alcatel-Lucent BBG9 S1:1 OHCTL Optical Hardware Control Module
  • Alcatel-Lucent FB16401-A-I03 GTD-5 Analog Master/Slave Control Board
  • Alcatel-Lucent MCR1721B Control Module
  • Alcatel-Lucent 9500-MPR 3DB20547ACAA01 ODU MPT-HC 11GHz Microwave Radio
  • Alcatel-Lucent 3HE01014AAAA02 Interface Module
  • Alcatel-Lucent 244-2091-005 High Density Digital Line Card V1.5
  • Alcatel-Lucent LAMBDAXTREME WWAA36 Optical Amplifier Module
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 6GHz 2P-2 Radio 3DB20444BAAA05
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC MPT-XP 6GHz 3DB20442BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 3DB20476ABAA01 Microwave Radio
  • Alcatel Lucent 3HE01019AAAA01 Module
  • Alcatel CPU5 3BA23071 PCB Card with IO2 3BA23050 Set
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20443BBAA02
  • Alcatel Lucent 500-1113-211 Rev H Channel Bank Assembly
  • Alcatel Lucent 89-0419-B-2 BA9ATS0FAB Frontal Compute Module
  • Alcatel-Lucent LambdaXtreme 1625 WWAF31 Optical Amplifier CP Module
  • Alcatel Z24 3BA53065 Analog Extension Card 3BA52065 AAAA KAZZB-01
  • Alcatel 3EH08263AAXX000448 OmniPCX Office Large PBX System
  • Alcatel Lucent VSEM-C 3FE62453 XA VAUCAJZKAA 7330 DSLAM Line Card
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20432BAAA04 18GHz Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20546ACAA01 11GHz Microwave Radio
  • Alcatel-Lucent 3DB04823AAAA Circuit Board
  • Alcatel-Lucent 3DB04530AAAA Circuit Board