Hardware description
The BAMU-12C Auxiliary measuring unit is a measuring unit for the accurate measurement of voltage and current. The unit has:
• Two three-phase voltage inputs
• Three current inputs
• LED indicator
• 24 V DC supply voltage
• Fiber optic link for communication with the upper frequency converter control unit.
compatibility
The measuring unit is compatible with the BCU-02, -12 and -22 control units. The control unit must also be equipped with a control that can communicate with the measurement unit
System procedures, such as IGBT power supply control procedures.
arrangement
Install the module in a cabinet/compartment in an indoor environment. Leave enough space for wiring. Make sure the temperature is not too high.
Do not install measuring units such as relays, contactors, brake choppers, power supply and motor cables near electromagnetic interference sources
Close. The minimum recommended distance from such parts is 200 mm (7.9 in). We recommend installing between the measuring unit and the source of interference
Install metal shielding. This shortens the distance required.
Install the control unit so that air can pass freely through the vent holes in the housing. Do not install directly on the heating device.
Mechanical installation
1. Install standard 35 × 7.5/15 mm DIN guide rails on the cabinet where the unit is to be installed.
2. Secure the two latches to the back of the measuring unit with four screws.
3. Connect the measuring unit to the guide rail as shown below.
4. Ensure that the guide rail is properly grounded through the assembly plate or the separate ground cable. The unit is grounded through a guide rail.
■ Communication link connection (V30)
Transmitter V1T, receiver V1R
Optical Fiber Communication Link: Avago Versatile Link Series optical transmitter and receiver, DC-50 MBd (50 Mbd/s)
■ Connect to the BCU control unit
Connect the BAMU-12C auxiliary measurement unit to the first unused channel of the BCU control unit via fiber optic cable.
norm
Input voltage 24 V DC ± 10%
Power consumption (24DVC power supply) 150 mA
Overvoltage Category OVC III
Pollution level PD2
AC/DC voltage limit 1250 Vrms/DC, 2.0kV peak
Allowable assembly position level
Distance from other components and control electronics 690 V AC basic insulation (8 mm [0.31 in])
Environmental condition
The BAMU-12C auxiliary measuring unit complies with the RoHS Directive (2002/95/EC).
No self-heating operating temperature: 0... +70 °C (32… 158 °F)
Storage temperature: -40... +85 °C (-40… 185 °F)
Maximum relative humidity: 90% (non-condensing)
Maximum working height: 4000 m (13123 ft)
Voltage measurement specification
Two identical, independent measurement channels. The two channels include three (phase) voltage inputs and neutral line inputs (U1,
V1, W1, N1 and U2, V2, W2, N2)
ID
Measuring range ±2.0 kV peak (phase to phase). The maximum voltage connected to the voltage measuring terminal is 600/690 V (DVC C).
The typical error is <0.5% at 25 °C (77 °F)
The maximum error is <1.25% over the entire temperature range
Current measurement specification
Range ±2.5 A peak
Input impedance < 0.5ohm
The typical error is <0.5% at 25 °C (77 °F)
The maximum error is <1.25% over the entire temperature range
Relevant standard
• Safety requirements: EN 50178 Electrical equipment for electrical installations
• IEC 61800-5-1 Semiconductor power converters for adjustable frequency drive systems
• UL 508C Industrial control equipment
• EMC Radiation: EN/IEC 6100-6-4:2007 Industrial Environmental Radiation Standard
EMC immunity: EN/IEC 61000-6-2:2005 Immunity to industrial environments
Choose Xiamen control Smith after sale worry
Excellent product quality
Only cooperate with manufacturers of first-line brands in the industry
Imports/Products
Good pre-sale service
Communicated with customers repeatedly about product model, quality, price and delivery date
Work with the customer to determine the best solution
Address user concerns in advance
Business execution in place
Ordered products delivered on time
Make perfect delivery plan to ensure the time limit
Assist users to handle the acceptance procedures
Perfect after-sales service
During the warranty period, problems will only be replaced and not repaired
Never put a problem on the back of your head
Service hotline 7x24 hours service
Solemn promise
1. All the items sold by the company, module card parts, etc., the quality problems arising from normal use during the warranty period are replaced free of charge, and there is no evasion.
2. For materials and equipment that have not been discontinued beyond the warranty period, only the cost of relevant parts will be charged for quality problems.
3. Provide replacement models and equipment replacement process services for discontinued materials and equipment.
4. Customers have purchased materials and equipment, lifetime free upgrade system software, related technical information provided free of charge.
5. Visit the use of materials purchased by customers from time to time, and solve any problems in time.
6. The company hotline provides 24-hour service, and the questions raised by customers are answered within 1 hour.
7. Not done, the company spirit of "thoughtful service, responsible to the end" attitude, from the customer's point of view to solve the problem, with serious and rigorous enterprise style, dedicated to each customer service.
email:1583694102@qq.com
wang@kongjiangauto.com