ABB REG216 Numerical Generator
ABB REG216 Numerical Generator
Application
The REG216 is intended for the protection of generators and block transformers.
The modular hardware and software design allows an extremely flexible installation. Simplicity of adaption to the size of the primary system and the desired protection schemes are achieved through the combination of a software library and hardware modules. Economic solutions can thus be achieved in the full range of applications for which it is intended.
The REG216 software system offers a library of protective functions. Functions suitable for generator and transformer protection are listed in the table below.
Different degrees of redundancy can be selected. Availability and reliability of the protection can be chosen to suit the application by duplicating e.g. auxiliary supply units of the whole system. Standard interfaces make REG216 compatible with different process control systems. Data exchange with higher process control levels are possible, e.g. one-way reporting of digital states and events, measured values and protection parameters. REG216 and REG216 Classic differ with regard to the binary process connection:
- REG216 uses the E/A-module 216GD61a.
- The REG216 Classic uses the modules 216GE61 / 216GA61 and 216GA62.
Features
• Modular hardware
• Selectable protection functions
• Multitude of applications
• Menu-assisted setting with PC
• Fully numerical signal processing
• Continuous self-monitoring of hardware
• Cyclical testing routines mostly performed by the software
• Setting of parameters and recording of the settings by PC
• Display of measured values
• Display of events, their acknowledgment and printout
• Disturbance recording
• Self-documentation
• Long-term stability
• Communication and coordination with station control
• Two design versions available; REG216 / REG216 Classic.
Protection functions
All protection functions required for the stand-alone protection of generators, power transformers and feeders are available. The system therefore replaces several relays of a conventional protection scheme for such power system equipment. The table on page 2 gives a survey of the most significant protection functions.
The desired protection functions to suit the particular application can simply be selected from a comprehensive library using the personal computer. No knowledge of computer programming is required.
All setting ranges are extremely wide to make the protection functions suitable for a multitude of applications. The following main parameters can be set:
• Allocation of processing units
• Input channel or channels
• Pick-up setting
• Time delay
• Definition of the operating characteristic
• Tripping logic
• Control signal logic.
Setting a corresponding parameter enables the protection functions to be "connected" to particular input channels.
Digital input and output signals can also be internally combined logically:
• The tripping outputs of each protection function can be assigned to channels of the tripping auxiliary relay assembly in a manner corresponding to a matrix.
• The pick-up and tripping signals can be assigned to the channels of the signalling auxiliary relay assembly.
• Provision is available for blocking each protection function with a digital signal (e.g. digital inputs or by using the tripping signal of another protection function).
• External signals applied to the digital inputs can be processed in any desired fashion.
• Digital signals can be combined to perform logical functions e.g. external enabling or blocking signals with the output signals of an internal protection function and then used to block one of the other protection functions.
email:1583694102@qq.com
wang@kongjiangauto.com