Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Horner APG HE693CALKIT simulation module

来源: | 作者:FAN | 发布时间 :2025-09-01 | 491 次浏览: | 🔊 Click to read aloud ❚❚ | Share:

Horner APG HE693CALKIT simulation module

Product Introduction

(1) Product Features

Horner APG HE693CALKIT calibration software is a computer program designed to support on-site and factory calibration of specific Horner APG simulation modules.

(2) Package composition

Each set includes: a floppy disk with calibration software, an RS-232 9-pin serial cable, a TTL to RS-232 converter, and an RS-232 ribbon cable with a 10 pin plug.

(3) Software operation requirements

Operating environment: Requires running on an IBM or compatible computer using DOS 3.1 or higher.

Hardware requirements: A text display is required and a serial port (COM1 or COM2) is used. The program defaults to using COM1.

(4) Module connection and preparation

The simulation module needs to be connected to the selected serial port on the computer through an RS-232 cable, combined with a TTL-to-RS-232 converter or an RS-232 ribbon cable with a 10 pin plug (depending on the simulation module to be calibrated).

The module does not need to be configured in the PLC, but appropriate power must be provided for the bus pins of the module.


Set conditions

(1) General Requirements (2.1)

Module installation: The module to be calibrated must be inserted into the PLC it will be used in the application; When inserting, the PLC must be powered off. After the module is correctly inserted into the PLC rack, the rack should be installed vertically (see Figure 1) to ensure good ventilation of the module; The PLC must be in 'stop' mode.

Stabilization time: After inserting the module into the PLC and completing the calibration connection, it needs to stabilize for at least 15 minutes after power on to ensure appropriate temperature balance.

Environmental requirements: Do not expose any equipment involved in the module or calibration process to extreme temperature changes; Calibration can be performed using an expansion rack.

(2) Set up process (2.2)

No additional special steps are required, and it should be carried out in conjunction with equipment preparation and module specific conditions.

(3) Equipment Requirements (2.3)

Calibrator: High quality calibrators (such as Omega CL511) must be used, and their accuracy must be more than twice that of the module (for example, THM884 has an accuracy of ± 1 degree Celsius, and the calibrator accuracy must be at least ± 0.5 degrees Celsius); It is recommended that all Horner Electric simulation modules use battery powered calibrators. When calibrating any thermocouple module, a battery powered calibrator must be used.

Wire requirements: The wire used for calibration must be the same as the wire used in the application, and must be of high quality with the shortest possible length; Avoid exposing wires to excessive radio frequency (RF) or electromagnetic interference (EMI) during the calibration process to prevent introducing errors.

(4) Module specific conditions (2.4)

1. Analog input module (2.4.1)

Covering HE693ADC406, HE693ADC405, HE693ADC415, HE693ADC410, HE693ADC420, the general requirements are as follows:

Calibrator: More than twice the accuracy of the module and powered by batteries.

Wire: Use high-quality wire that is the same as the wire used in the application and has the shortest length.

Environment: Avoid exposing the module to excessive EMI or RF, extreme temperature changes.

Installation and status: The module needs to be inserted into the PLC slot used in the application, and after being powered on and connected, it should be stable for at least 15 minutes. It should be installed vertically (in the panel installation position), and the PLC should be in "stop" mode; The unused channels during the calibration process of HE693ADC406 need to be short circuited and grounded.

2. Analog output module (2.4.2)

Regarding HE693DAC410 and HE693DAC420, it is required to be consistent with the analog input module (except for the channel short-circuit grounding of HE693ADC406).

3. Resistance Temperature Detector (RTD) module (2.4.3)

Including HE693RTD600, HE693RTD601, HE693RTD660, HE693RTD665, HE693RTD666, in addition to meeting the general requirements of the analog input module, there are additional requirements: unused channels during calibration must be short circuited and grounded; Modules with a suffix of -20 need to use the a=d switch (PT100D) in the calibration software.

4. Strain gauge module (2.4.4)

Including HE693STG883 and HE693STG884, it is required to be consistent with the RTD module (without using channel short-circuit grounding).

5. Thermocouple module (2.4.5)

Covering multiple models such as HE697THM160 and HE693THM166, in addition to meeting the general requirements for analog input modules, there are additional requirements: modules with a suffix of -21 need to use external ISOBLK for cold end compensation; During the calibration process, the last channel needs to be short circuited and grounded to optimize cold end compensation; Modules with suffix -02 need to use the "=k" switch in the executable file (refer to section 4.1).

Calibration process

(1) General Instructions (3.1)

The general calibration process is only a basic framework, with slight differences in the calibration process of each module, but the core logic is consistent. The simulation module needs to be calibrated according to the specific process described in the subsequent sections; Table 3.1 lists the simulation modules and their corresponding calibration files, with some corresponding relationships as follows:

Product model calibration software Product model calibration software

HE693ADC405 adc4x5.exe HE693THM166 thm166.exe

HE693ADC410、HE693ADC420 adciso.exe HE693THM665、HE693THM666、HE693THM668 thm668.exe

HE693ADC406 adc406.exe HE693THM884(REV. A,B,C) thm884_1.exe

HE693DAC410、HE693DAC420 daciso.exe HE693THM884(REV. D,E,F,G,H,HX,J,K,L) thm884_2.exe、THM884cal.exe(Windows  Version)

(2) Software startup (3.2)

1. Startup steps

Select the corresponding executable file from the floppy disk list (for example, calibrate HE693THM884 and select Thm884. exe).

Enter the corresponding command at the DOS prompt to run the calibration program: when using the COM1 port by default, enter "Thm884" and press "ENTER"; When using the COM2 port, enter "Thm884=C2" and press "ENTER".

To view command line switches and their instructions, enter "Thm884=?" at the DOS prompt and press "ENTER".

2. Screen Example (3.2.1)

After the program starts, the top of the screen will display the program name and version. Taking the THM884 thermocouple module calibrator (V2.04) as an example, the screen will display channel values, types, scales, zero points, and other information, as well as module models, channel quantities, hardware alarms, versions, and other parameters. At the same time, it will prompt the functions of each function key (F1-F9, Esc) (such as F1 calibration of J-type thermocouples, Esc exit, etc.).

3. Windows version software installation and operation (3.2.2, 3.2.3)

Installation: Load the floppy disk containing the THM884cal.exe (Windows version) installation file, locate and select the setup. exe file, follow the prompts to select the application file storage directory, and after installation is complete, you can use it.

Run: Find THM884cal.exe in the directory specified during installation, double-click the file to open the application; This version operates similarly to the DOS version. If you have any questions about the functionality, press the F12 key to access the help file.


(3) Process Overview (3.3)

Disable non-volatile random access memory (NVRAM): If the "disable" option is not provided, it will be automatically disabled. This step closes the old calibration constant and uses the default value for new calibration. The module needs to be reset to use the default value.

Disable PLC configuration: Make the module use default values (the module defaults to PLC configuration mode when powered on).

Initialization module: Execute after disabling PLC configuration.

Perform calibration: If it is a thermocouple module, you need to first select the calibration type. The software will prompt you for each step in the calibration process, and you need to follow the prompts.

Update NVRAM: Update the new default values to NVRAM.

Activate NVRAM: Enable the module to use the stored calibration constants the next time it is powered on.

Re initialize the module: Let the module re read the calibration and filtering constants from the NVRAM.

(4) Module specific calibration process (3.4)

The calibration steps and corresponding function keys for each module are as follows (some module examples):

1. Analog input module (3.4.1)

Taking HE693ADC406, HE693ADC405/415, and HE693ADC410/420 as examples:

Step Process Function Key

1. Disable NVRAM F5

Initialization module F6

3. Disable PLC configuration F8

Perform calibration (follow software prompts) F1

5 Update NVRAM (store new constants, select "Yes") F3

Activate NVRAM F4

7 Initialization module F6

2. Analog output module (3.4.2)

The calibration steps for HE693DAC410 and HE693DAC420 are the same as those for the analog input module. It should be noted that when calibrating the analog output module, the PLC must be in non operating mode.

3. RTD module (3.4.3)

HE693RTD600 and other models:

Step Process Function Key

1. Disable NVRAM F7

Initialization module F6

3. Disable PLC configuration F8

Perform calibration (follow software prompts) F1, F2, F3

5. Update NVRAM (store new constants, select "Yes") F5

Activate NVRAM F7

7 Initialization module F6

4. Strain gauge module (3.4.4)

The calibration steps for HE693STG883 and HE693STG884 are the same as those for the analog input module.

5. Thermocouple module (3.4.5-3.4.7)

HE697THM160, HE697THM260: Follow the same steps as the RTD module.

HE693THM166: The steps are consistent with the analog input module.

HE693THM406 and other models: The steps are consistent with the RTD module.

HE693THM884 (K-type+channel offset calibration): Use THM884_K.bat batch file, consisting of 15 steps, including module installation, power on, NVRAM disable/activate, PLC configuration disable/enable, calibration execution, offset setting and transmission, NVRAM update, module initialization, etc. Some steps require the use of function keys such as F1, F4, F5, F6, F7, F8, and finally remove the module after power off.

HE693THM894 (K-type calibration): Use the THM894_K.bat batch file, following the same steps as HE693THM884 (K-type+channel offset calibration).


Switch settings

(1) Switch Description (4.1)

Many simulation modules can be temporarily configured and software switches can be used, such as observing the reaction of thermocouple modules using T-shaped thermocouple wires (rather than the commonly used J, E, R types); Please note that the=T,=K, and=C switches are volatile and will not cause permanent changes to the module, while commands such as=NVRAM (such as=S) will cause permanent changes. The switch format is "Thm884 [=C1] [=C2] [=T] [=K] [=Snnnn. n, nnnn. n, nnnn. n,...]", and the functions of each switch are as follows:

Switch Function Description

=C is used to select serial ports, for example=C1 (COM1),=C2 (COM2)

=T represents test mode, still transmitting command messages, but variables use internal values, receiving messages generated by simulation (software simulation mode), without the need to connect modules

=K sets the calibration type to K instead of the default J type

=Set calibration scale points for S, separated by commas (without spaces), in the order of K (or J) median, K high value, E median, E high value, R median, and R high value; When the value is 0, use the default value; If there are less than 6 entries, the remaining entries will use default values; The scale point must not be lower than 25 degrees Celsius (this low-temperature calibration point is crucial for optimizing cold end compensation)

(2) Example (4.2)

Command function

Thm884=C1 specifies COM1 as the serial port (default port)

Thm884=C2 specifies COM2 as the serial port (this command needs to be called to use COM2)

Thm884=T Enable test mode, transmit commands but only simulate messages, do not store values

Thm884=K sets the calibration type to K type (default J type), suitable for special applications and European calibration

Thm884 =S600.0,700 

  • MEYER MEYER0909 1RR1337001 Industrial Control Module
  • MICRO MC2-440-10TVB-1-20 Industrial Switch Data
  • MICROSET 104988-E03 Control Card Data
  • MILLIPORE WGGB12S02 Water System Module
  • MILLIPORE CMHT-11S02 Chemical Process Sensor
  • MINI MAESTRO 60X7/14 Servo Drive Technical Data
  • MITRA PE3257/03 High Frequency Transformer
  • MEYER MEYER1009 1RR1337001 Industrial Control Component
  • MICRO MPB1-TP Industrial Interface Terminal Module
  • Mitsubishi GU-D04 GOT Serial Communication Board
  • Mitsubishi R28TB Robot Teaching Pendant
  • Mitsubishi A1S68DAV 8-Channel Analog Output Module
  • Mitsubishi A1S65B-S1 Expansion Base Unit
  • Mitsubishi A1SJ51T64 I/O Link Master Module
  • Mitsubishi HC-KFS23K-S49 AC Servo Motor
  • Mitsubishi ST1X4-DE1 4-Channel Digital Input Module
  • Mitsubishi QM100HY-H IGBT Power Module
  • Mitsubishi QM100HY-H IGBT Power Module
  • Mitsubishi QM100DY-H IGBT Power Module
  • Mitsubishi BN624A96IG52A MELSECNET/H Fiber Module
  • MITSUBISHI BN624A960H03B Control Module
  • MIYACHI MA-201C Welding Control Unit
  • MKS 223BD-00001AAB Pressure Transducer Data
  • Modicon AS-BADU-204 Analog Input Module Data
  • Modicon AS-S908-120 Remote I/O Processor
  • Modicon AS-J890-002 Remote I/O Interface
  • Modicon NW-BM85D002 Modbus Plus Bridge Manual
  • Modicon AS-B875-002 24VDC Input Module Data
  • MKS T3BIB-29916 Control Interface Board
  • MKS 683B-23795 Capacitance Manometer Pressure Sensor
  • Molex 85003-0567 DIN 41612 Connector
  • MOORE 750E1B2GNNNF Temperature Transmitter
  • MOORE 16147-51-2 ACM Transition Board
  • MOORE 16147-51-02 Signal Isolator
  • MOORE 16407-1-1 Industrial Power Module
  • MOORE 42-30 Smart Electro-Pneumatic Positioner
  • MOORE 16310-71-1 Industrial Control Module
  • MOTOMAN HW9381022 Welding Robot Arm
  • MOX MX603-2007-01 Industrial Control Module
  • MOXA EDS-408A-MM-SC Industrial Ethernet Switch
  • M-SYSTEM MD2202-D32-X-P Digital Input Module
  • MTL 8811-IO-DC Digital I/O Module
  • MTL 8604-FT-FU Field Terminal Specification
  • MTL 8104-AO-IP Analog Output Module
  • MTL 8103-AI-TX Analog Input Specifications
  • MTL 8505-BI-MB Bus Interface
  • MTL 8711-CA-NS Carrier Module Specification
  • MTL MTL5514D Intrinsically Safe Interface Module
  • MTL MTL4544AS Isolating Interface Module
  • MTL 8715-CA-BI HART Transparent Isolator
  • MTL831B Analog Multiplexer Transmitter
  • MTL 8502-BI-DP Profibus DP Interface Module
  • MTL838B-MBF Modbus Analog Multiplexer Receiver
  • MTL5053 Fieldbus Intrinsic Safety Barrier
  • MTL 8939-HN Fiber Optic Extender IOTA
  • MTL 8937-HN Dual-Channel Zener Barrier
  • MTL 5541 Repeater Power Supply Barrier
  • MTL 4073 Passive Intrinsic Safety Barrier
  • MTL5541 Galvanic Isolated Barrier
  • MTL 2213 Isolated Intrinsic Safety Barrier
  • MTS TBF120/12TS Servo Amplifier
  • MTS TBF120/7R Resolver Servo Amplifier
  • MULLER COAX MK32NC Coaxial Connector Module
  • MURATA DCC2223A 3EST125-977 Power Filter Module
  • MURR 857781 Industrial Interface Module
  • MYKROLIS FC-280SAV Gas Flow Control Module
  • Nabtesco BTC-304 Brake Controller
  • NACHI UM356B Industrial Module Analysis
  • NACHI MFMA452D5V3 Servo Motor Specification
  • NACHI BUY222 Robotic Control Component
  • NAI 64SD1-08KRF1-13 Synchro-to-Digital Data
  • NAICH AUX111 Auxiliary Contact Specification
  • NAIS ANR5131 Micro Laser Sensor Controller
  • NATIONALA MM-4M-R Industrial Control Module
  • NEC FC-9821X MODEL2 Factory Computer
  • NEC FC-9801F Legacy Industrial Computer
  • NEC FC-9821X MODEL1 Industrial Computer
  • NEC FC-9821KE Industrial Panel PC
  • NEC RSA-983/D Embedded Industrial Computer
  • NEC G8NXAA5G Industrial Controller
  • NEC 136-551735-D-04 Genius Bus Interface
  • NEC SC-UPCIN-3 Industrial Control Module
  • NEC PC-9821XB10 Industrial Control Computer System
  • NEC 136-553623-A-01 Industrial Network Communication Module
  • NEC 136-551973-A-01 Control Processing Board
  • NEC 136-551733-B-02 Industrial Control Interface Module
  • NEUGART PLE120/115 Gearbox
  • NEUGART PLE120 Planetary Gearbox
  • NEXUS CONTROLS 369B1843G5009 Technical Data
  • NI NI-9694 Digital I/O Breakout
  • NI SBRIO-9627 Embedded Single-Board
  • NI SCXI-1102C Amplifier Module
  • NI sbRIO-9627 783817-01 Embedded Controller
  • NI GPIB-140A 186135G-01 GPIB Controller
  • NI GPIB-140A 186135F-31 GPIB Interface Card
  • NI GPIB-140A 186135H-01L Fiber Optic Extender
  • NI 192061B-02 Shielded DAQ Cable
  • NI SCXI-1346 Multi-Chassis Cable Adapter
  • NI SCXI-1600 USB Data Acquisition Module
  • NIBCO WD2000 Ductile Iron Butterfly Valve
  • NIKUNI 25KLD07Z-M Magnetic Drive Pump
  • NMB MAT 2410ML 05W B50 Industrial Cooling Fan High Reliability
  • NMS CG6565 64 2L 8TE Communication Gateway High Capacity Network Module
  • NMS CG6060 32 4TE1 Communication Gateway for Network Systems
  • NOVELLUS 02-113640-00 Industrial Control Module System Component
  • NOVOTRON ND32-5610VS-001-000-00 Drive
  • NYQUIST IOB-80 I/O Interface Board
  • OBERG INDUSTRIES F-DMDM-PM-110E Specifications
  • OCM 44A737830-001R04 Module
  • OEMAX NX-BASE08 8-Slot Base Plate Manual
  • OEMAX NX-BASE05 5-Slot Base Plate
  • OEMAX NX-CPU750B Basic PLC CPU
  • OEMAX NX-CPU750C High-Performance PLC CPU
  • OEMAX NX-Y16R 16-Point Relay Output Module
  • OEMAX NX-RTD8 8-Channel RTD Input Module
  • OEMAX NX-SLAVE Remote I/O Slave Module
  • OEMAX NX-SCU Serial Communication Unit
  • OEMAX NX-POSI2 2-Axis Positioning Module
  • OEMAX NX-DUMMY Dummy I/O Module
  • OEMAX NX-CPU700P PLC Controller
  • OEMAX NX-BASE10 PLC Backplane
  • OEMAX NX-AO4C 4-Channel Analog Output Module
  • OEMAX NX-AI8C 8-Channel Analog Input Module
  • OMACO GF0-57CQD-002 Industrial Control Module Precision Automation
  • OPTIMATE OP-620 Industrial Automation Control Module
  • OPTIMATE OM1510 Industrial Control Module Performance Solution
  • OPTO 22 SNAP-IDC5D Digital Input Module for Automation
  • OPTO 22 SNAP-AITM-2 Thermocouple Module