Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Schaffner Ecosine ® Economy Line FS 42842 Compact Passive Harmonic Filter

F: | Au:FAN | DA:2026-04-03 | 597 Br: | 🔊 点击朗读正文 ❚❚ | Share:


Ecosine ®  Deep Technical Analysis of Economy Line Passive Harmonic Filter: Reshaping Power Quality with FS 42842 Series

Introduction: Challenges of Power Quality and Harmonic Control in Modern Industrial Environment

In highly automated modern industrial and electrified infrastructure, power quality has become a core indicator that determines system stability and energy efficiency. With the large-scale deployment of frequency converters, uninterruptible power supplies (UPS), and high-power DC fast charging equipment, traditional linear loads are gradually being replaced by nonlinear loads. These nonlinear loads, especially those using 6-pulse diodes or thyristor SCR rectifiers, will absorb non sinusoidal currents from the power grid during operation, resulting in a large amount of harmonic currents.

The overflow of harmonic currents can cause a series of serious engineering problems: it can cause additional copper and iron losses in transformers and cables, leading to abnormal heating; Causing bus voltage distortion and increasing the risk of system resonance; It may even interfere with the normal operation of sensitive electronic devices, causing unpredictable production downtime. In order to address these challenges, the International Electrotechnical Commission (IEC) and national standard organizations have established strict electrical energy quality standards, such as EN 61000-3-12 and IEEE-519. In this context, Schaffner launched Ecosine ®  Economy Line passive harmonic filters, especially the FS 42842 (50 Hz) series, provide engineers with a standardized harmonic control solution that combines high efficiency and cost-effectiveness.


Core positioning and compliance: Accurately meet engineering requirements with THDi<10%

The FS 42842 series is clearly defined as an "economical product line" in the Schaffner product matrix. The core design goal is not to pursue ultimate harmonic elimination (such as the<5% THDi achievable by the Schaffner ecosystem evo series FN 3440/50), but to precisely target the highly cost-effective engineering sweet spot area of THDi (total harmonic current distortion rate) ≤ 10%.

For nonlinear three-phase equipment that extensively uses B6 (six pulse) rectifier front-end, a 10% THDi index is a key compliance watershed. According to the technical documentation, FS 42842 can ensure that the total harmonic current distortion rate of the input current is strictly controlled within 10% when equipped with a DC link reactor; Even under the worst-case conditions without DC link reactors, its THDi can be limited to within 15%.

This performance directly endows the device with strong standard compliance capabilities:

EN 61000-3-12 compliance: easily meets the most stringent harmonic emission limit requirements for devices with rated current ≤ 75A (per phase) in the European market.

IEEE-519 compliance: In common power grid environments with an Isc/IL<50, it fully complies with the standard's requirements for Total Demand Distortion (TDD) limitations.

By quickly and easily upgrading standard motor drives to "low harmonic drives," companies can cross the threshold of power quality compliance without having to bear the high cost of active filters.


Panoramic deconstruction of technical architecture and performance indicators

The reason why the FS 42842 series can achieve excellent filtering effects in a compact volume is due to its ingenious passive filtering topology design. The following is a deep analysis of its core technical specifications:

1. Wide power coverage and high performance

This series of filters covers a rated motor drive input power range from 4 kW to 160 kW (@ 400 VAC/50 Hz), and the maximum supported power can reach 200 kW in a 500 VAC/50 Hz grid. In terms of energy efficiency, modern industry is extremely sensitive to the parasitic losses of the filters themselves. FS 42842 has an efficiency of over 98% at rated line voltage and power. From the data in the selection table, it can be seen that even the 160 kW FS 42842-320-99 model has a power loss of only 988W under rated load, which is outstanding among similar passive filtering devices and effectively avoids the embarrassment of "increasing energy consumption instead of harmonic control".

2. Strong impact resistance and safety protection mechanism

Motor drives in industrial sites often face heavy load starting and instantaneous overload. FS 42842 has an overload capacity of 1.6 times the rated current for 1 minute (once per hour), perfectly matching the typical overload cycle of motor drive. In addition, its short-circuit current rating (SCCR) is as high as 100 kA, which means that in the event of extreme short-circuit faults, the filter can withstand huge short-circuit electric forces without causing explosions or secondary disasters, greatly improving the overall safety of the system.

In terms of insulation and voltage resistance, the filter has passed a high voltage test of 2500 VAC (lasting for 2 seconds) between phases and ground, and uses flame-retardant materials that comply with UL 94 V-2 or better standards to physically block fire hazards.

3. Environmental adaptability and reliability design (MTBF)

The environment in industrial sites is often harsh and ever-changing. FS 42842 adopts internal fan cooling (non adjustable) in the cooling design, combined with IP20 protection level, to meet the installation requirements of most electrical control cabinets. Its working temperature range is extremely wide:

-25 ° C to+45 ° C: Full load and full power operation;

+45 ° C to+70 ° C: derating operation (following the derating formula:

Iderated=Inominal×(70∘C−Tamb)/25∘CI derated=I nominal× (70 ∘C−T amb)/25 ∘C); -25 ° C to+70 ° C: meets transportation and storage requirements.

Based on the military standard Mil-HDBK-217F, the mean time between failures (MTBF) under 45 ° C and 500V operating conditions exceeds 200000 hours (approximately 22.8 years), demonstrating its extremely high long-term operational reliability, particularly suitable for the petrochemical, water treatment, and metallurgical industries that require high continuous production.

4. Compatibility of grounding system

The document clearly states that FS 42842 supports three mainstream grounding systems: TN, TT, and IT. This makes the filter not only suitable for domestic TN-S/TN-C-S systems, but also perfectly adapted to common TT systems in Europe and some IT isolation grounding systems that require extremely high power supply continuity, such as medical facilities or mines.


In depth application scenarios: from traditional pump fans to new energy fast charging

The selection of passive harmonic filters must be deeply matched with their front-end load characteristics. The document clearly states that the performance parameters of FS 42842 are based on a six pulse diode rectifier. For the front-end of a thyristor (SCR) rectifier, the triggering angle of the thyristor can cause a shift in the harmonic spectrum, and the actual treatment effect may vary, requiring specific evaluation.

Scenario 1: Motor drive in pump and fan applications

In HVAC (Heating, Ventilation and Air Conditioning), water treatment plants, and industrial cooling systems, pumps and fans account for a significant proportion of electricity consumption. These scenarios typically use standard 6-pulse frequency converters. Installing FS 42842 directly at the input of the frequency converter not only suppresses THDi to below 10%, but more importantly, it can "release" the additional load and heat caused by harmonics in the electrical infrastructure. Due to the fact that harmonic currents (especially 5th and 7th harmonics) do not stack on the neutral line in a three-phase four wire system, the temperature rise of transformers and cables is effectively reduced, thereby improving the actual utilization rate of electrical system capacity.

Scenario 2: DC fast charging pile for electric vehicles

With the outbreak of new energy vehicles, high-power DC fast charging stations have become the hardest hit areas for harmonics. The DC fast charging module is essentially a high-power AC/DC rectifier. The document lists' battery chargers, including DC fast charging for electric vehicles' as a typical application. In commercial complexes or centralized charging stations, multiple fast charging piles working simultaneously can generate huge superimposed harmonics, which can easily trigger fines from power grid companies or cause transformer trips within the station. By batch configuring FS 42842 at the front end of the charging module, it is possible to ensure that the current distortion rate of individual piles and the entire station meets the grid connection requirements of IEEE-519 or the local power grid, reduce the risk of system resonance, and protect the precision billing and control equipment in the charging station from harmonic interference.


Guidelines for Engineering Selection, Parallel Logic, and Mechanical Installation

The correct selection and installation are the key to ensuring the maximum performance of the filter. In engineering practice, many electrical engineers often make the mistake of selecting harmonic filters based on current (this is a common practice for EMC/EMI filters). The document issued a clear warning regarding this: "As harmonic filters can reduce the input RMS current, it is not recommended to select harmonic filters based on current ratings like EMC filters.”

The correct selection logic for FS 42842 must be based on system voltage and load (motor drive) power.

1. Analysis of Selection Table Data

Taking the 400VAC/50Hz system as an example:

Small scale drive: such as the 4kW FS 42842-10-44, which weighs only 10kg and has a loss of 63W, is very suitable for small conveyor belts or micro water pumps.

Medium sized drive: such as the 45kW FS 42842-90-35, weighing 47kg with a loss of 493W, is standard for large central air conditioning chillers.

Large scale drive: such as the 160kW FS 42842-320-99, weighing up to 135kg and designed with -99 terminals, suitable for municipal high displacement sewage pumping stations.

It is worth noting that in the 500V system (such as 160kW corresponding to 200kW), due to the increase in voltage and decrease in current, the loss of the filter itself does not significantly increase, reflecting good wide voltage adaptability.

2. Engineering rules for parallel connection of multiple loads and filters

In practical power distribution design, it is common to encounter multiple nonlinear loads connected in parallel. Schaffner offers two solutions:

Single filter for multiple loads: Several motor drives can be connected in parallel to a filter, provided that the rated power of the filter is equal to or greater than the sum of the power of the connected drives. It is strongly recommended to use drivers with built-in DC reactors to achieve the best governance effect.

Filter parallel mode: When the total required power exceeds the maximum rated value of a single filter (such as over 200kW) and non-standard customized solutions are not desired, two or more filters can be connected in parallel. The engineering red line is that filters with equal rated power must be used in parallel to ensure equal current flow between internal reactors. Parallel connection of filters with unequal power can cause overload and burnout of low impedance branches.

3. Mechanical dimensions and electrical terminal specifications

To accommodate the depth limitations of different cabinets, the FS 42842 series offers 5 mechanical size architectures:

The most compact FS 42842-10 to -16 models, with dimensions of only 390 × 185 × 190mm, are suitable for small control boxes with limited space.

The largest FS 42842-260 to -320 models, measuring 700 × 450 × 385mm, typically require independent standard electrical cabinets for installation.

In terms of wiring terminals, the document provides extremely detailed torque parameters from small power 16 AWG (1.5 mm ²) to large power 1/0 AWG (50 mm ²), such as a 35 mm ² wire diameter corresponding to 7-8 Nm of torque. Strictly adhering to these torque values is crucial to prevent local overheating caused by poor contact. In addition, all external wiring must use UL rated fuses for short-circuit protection.


System Requirements and Disclaimer: Must Read Notice for Professional Engineers

Any high-end passive component has preconditions for its operating environment. To achieve the promised<10% THDi metric in the data manual, FS 42842 must meet the following system level requirements:

Power grid voltage distortion rate (THDv)<2%: If the factory's superior power grid already has severe voltage distortion, passive filters may experience resonance amplification and fail to achieve the expected filtering effect.

Three phase voltage imbalance<1%: Severe three-phase imbalance can cause saturation of the internal inductance of the filter, leading to magnetic bias risk.

At the same time, following industrial product compliance practices, Schaffner declared a standard disclaimer at the end of the document: the applicability of the product is ultimately determined by the customer and must never operate beyond the published specifications. This reminds integrators that under extreme working conditions (such as a decrease in heat dissipation capacity due to an altitude exceeding 1000 meters, or a frequency deviation of 50Hz), corresponding derating conversion is required.


  • ENOTEC OXITEC 5000 SME-53310000 Oxygen Analyzer
  • SIGMATEK Krauss Maffei PC301-K 01-310-301-K Industrial PC
  • SIGMATEK SDD310-23 VARAN Servo Drive
  • SIGMATEK CDM 163 and CIC 011 C-DIAS Input Modules
  • SIGMATEK MDP 101-1 Power Module
  • SIGMATEK CM5V020 Wiring Circuit with CTMS020
  • SIGMATEK CCP521 C-DIAS Processor Module
  • SIGMATEK MDP 101-K Power Module
  • SIGMATEK ETEK C-IPC 733MHz VIA Eden 7000
  • SIGMATEK DCP 643 DIAS PLC CPU Module
  • SIGMATEK TAE121 12-200-121 Operator Terminal
  • Sigmatek TMS012-T Injection Moulding Technology Module
  • Sigmatek MDD 121-1 Controller
  • Sigmatek CDM167 Module
  • Sigmatek DCP082 DIAS Central Unit
  • Sigmatek ETT731 Built-In Terminal Touch
  • Sigmatek CCP521 C-DIAS Processor Module
  • Sigmatek Krauss Maffei PC301-K Control Cabinet PC
  • Sigmatek CIC-21 C-DIAS CAN Module
  • Sigmatek CIO-011 Multi I O Module
  • Sigmatek 01-450-152D C-IPC 152 Industrial PC
  • SIGMATEK 01-450-024 C-IPC 128MB VIA 733MHz
  • SIGMATEK CCL-081 C-DIAS Processor Module
  • SIGMATEK CP311 20-004-311 Module
  • SIGMATEK EP00000262 SLIDES MIDI I O-V3 Controller
  • SIGMATEK TMS012-T Slides Technology Module
  • SIGMATEK MDD111-1 Drive Axis Module
  • SIGMATEK MDP101-1 PLC Module
  • SIGMATEK CP111 S-DIAS Processor Module
  • DEMAG ErgoControl Sigmatek NC4 Display Unit
  • SIGMATEK DCP642 Module
  • Sigmatek Demag NC4 9617.067.03 Control Module
  • Sigmatek DCP 643 Central Processing Unit
  • Sigmatek VI 021 S-SLIDES VARAN Interface Module
  • Sigmatek SDD340-46 Servo Drive 14kVA
  • Sigmatek DSI021 Slide Siemens Interface
  • Sigmatek CCL912 C-SLIDES CPU PSU Module
  • Sigmatek ETV1521 VARAN Control Panel
  • Sigmatek ET322 Operator LCD Terminal
  • Sigmatek MDD1111 DIAS Drive Module
  • Sigmatek CAM123 Module
  • SIGMATEK CP111 VARAN Ethernet Controller
  • SigmaTek MDD 111 Axle Module
  • SIGMATEK CIO013 C-DIAS I O Module
  • SIGMATEK AKM52K-ANC2GBB0 Servomotor 640VDC
  • SIGMATEK ETT321 01-230-321 Touch Screen
  • SIGMATEK NC4Kompakt 01-250-010-D Safety Controller
  • SIGMATEK CIO011 C-DIAS Multi I O Module
  • SIGMATEK MDD 121-1 Drive Axis Module
  • SIGMATEK CDM163 Control Module
  • Sigma-Tek 4000HR-3 Heading Reference Directional Gyro
  • Sigmatek DIAS DAI 883 Analog Input Module
  • Sigmatek 0332.554.03 Printed Circuit Board Card
  • Sigma Tek 5000B-36 Attitude Gyro 8130
  • Demag NC4 0332.554.03 Sigmatek Control Board
  • Sigmatek IPC Pentium 300 CF Industrial PC
  • Sigmatek MDP 102 PLC Module
  • Sigmatek DTO163 Digital Output Module
  • Sigmatek PCT151 Touch IPC 15 Panel and I-PC C300
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SCP011 S-DIAS Safety CPU Module
  • Sigmatek SE051 Network Splitter Module
  • Sigmatek CIO011 C-DIAS I O Module
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SDD310-4 DIAS Drive 14kVA
  • Sigmatek CTMS020 C-DIAS Technology Module
  • Sigmatek CTMS020 CD Technology Module
  • Sigmatek CTO167 C-SLIDES Digital Output Module
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek SDD310-4 SLIDES Drive 310
  • SIGMATEK MDP 102-1 DIAS Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU Industrial
  • SIGMATEK CAO081 Analog Output Module
  • SIGMATEK DCC080L Control Module
  • SIGMATEK MDP101-1 Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU
  • SIGMATEK PC325-K Industrial PC
  • SIGMATEK ETT 731 Operator Terminal
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK 12-780-012 R8-IPC Industrial Computer
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek DAI 883 DIAS Analog Module
  • Sigma Tek 4000B-30 Directional Gyro
  • Sigmatek CP112 S-DIAS Processor Module
  • Sigmatek SDD310 DIAS Drive
  • Sigmatek SDD120-23 DIAS Drive 14kVA
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek CIV513 VARAN Control Module
  • Sigmatek DCP 082 Processor Module
  • Sigmatek C-IPC Industrial PC 01-450-023 GEB
  • SIGMATEK PC572 Operating Terminal
  • SIGMATEK DCC041 DIAS Compact Controller HW 6.10
  • SIGMATEK C-IPC 152 1GB Celeron M440 Controller
  • SIGMATEK 01-310-322-K PC322-K Industrial PC
  • SIGMATEK TAE732-P Touch Screen Operator Panel
  • SIGMATEK 01-018-100 Control Module
  • SIGMATEK DDI-164 Digital Input Module
  • Sigma-Tek 5000B-36 Artificial Horizon
  • SIGMATEK 12-780-012 R8-IPC Geode LX800 Computer
  • SIGMATEK CTMS 020 Servo Drive
  • Sigmatek MDD121-1 Controller
  • Sigmatek ETV1021-L VARAN Terminal
  • Sigmatek DST022 DIAS Module
  • Sigmatek CCP512-K C-Dias Processor Module
  • Sigmatek SRO 021 Relay Output Module
  • Sigmatek SDI 101 Digital Input Module
  • Sigmatek IPC 221 Industrial PC
  • Sigmatek DNC-305 Digital Input Module
  • Sigmatek SDD335 DIAS Drive
  • Sigmatek C-IPC Industrial Controller
  • SIGMATEK 01-450-031 C-IPC 256MB LX800 Computer
  • SIGMATEK SDD310-3 DIAS Drive 310
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK CNC031 CD Analog Module 12-011-031
  • SIGMATEK 01-450-031 C-IPC 256MB LX800
  • SIGMATEK 01-450-026 C-IPC VIA 733MHz Controller
  • SIGMATEK DCP-643 DIAS CPU Module with DKL-003
  • SIGMATEK MDD111-L DIAS Drive Axis Module
  • SIGMATEK SDD310-23-L DIAS Drive 310
  • SIGMATEK Viscotec ETV0551 Touch Panel
  • SIGMATEK PC321K Industrial Computer
  • SIGMATEK MDP 102-1 SLIDES Power Module
  • SIGMATEK TAE-151 12-200-151 Light Terminal
  • SIGMATEK CP102 20-004-102P6995B HMI Panel
  • SIGMATEK CAM-123 12-017-123-C Analog Mixing Module
  • SIGMATEK DCC041 DIAS Compact Controller
  • SIGMATEK DVI021 and DKL015 DIAS Power Module