Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

WOODWARD 2301E Digital Speed Controller

F: | Au:FAN | DA:2026-04-16 | 874 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Woodward 2301E Digital Load Distribution and Speed Controller: Practical Engineering Configuration, Debugging, and Troubleshooting

In the field of generator set control, whether it is a diesel engine or a gas engine driven generator, achieving precise speed regulation and stable load distribution is the core to ensure power quality and system reliability. The Woodward 2301E digital controller is a classic product designed for this purpose. It is based on a microprocessor and not only inherits the functions of the 2301A and 2301D analog controllers, but also adds more advanced control features through software flexibility, making it an ideal choice for upgrading old control systems or building new projects.

This article will deeply analyze the hardware integration points, software configuration process, core control algorithms, dynamic tuning methods, Modbus communication settings, and systematic troubleshooting strategies of the controller based on the 2301E installation operation manual (Manual 26641) from the perspective of frontline engineering personnel. It provides a practical technical guide for engineers engaged in generator set debugging, maintenance, and modification.


Hardware installation and wiring: laying the foundation for reliable operation

There are two ordering numbers for the 2301E controller: 8273-1011 (for regular use) and 8273-1012 (for hazardous use). Both are metal chassis with a single circuit board design, connected to an external computer via a 9-pin RS-232 port for configuration.

1. Power and environmental requirements

The controller requires a DC power supply of 18 to 36 Vdc, with a typical power consumption of ≤ 20W and a maximum current of approximately 600mA. The power supply must come from a SELV (Safety Extra Low Voltage) certified power supply/battery charger. The ambient temperature range is -40 to+70 ℃, and it can be installed inside the control cabinet, but it is strictly prohibited to install it directly on the engine. For hazardous locations (Class I, Division 2, Groups A, B, C, D), the final installation enclosure must achieve IP54 protection level and meet the requirements of IEC 60079-0.

2. Key wiring terminals

Power supply (terminals 48, 49, 50): The positive terminal is connected to 48, the negative terminal is connected to 49, and 50 are optional protective grounding (PE) connection points. It is recommended to use shielded twisted pair cables for the power cord, with the shielding layer grounded at a single point on the controller end.

Speed sensor (terminals 25, 26, 27): connected to a magneto resistive speed probe (MPU). The frequency range is 100-25000 Hz, and the voltage range is 1.7-35 Vac (≥ 1.0 Vrms required for startup). Use shielded wire and connect the shielding layer to terminal 27 (chassis).

PT/CT input (terminals 1-9): The three-phase voltage (PT) is connected to terminals 1-3 (line voltage 90-120 Vac or 200-240 Vac), and the three-phase current (CT) is connected to terminals 4-9 (5A secondary side). CT burden is less than 0.1 VA/phase. Attention: The CT secondary side must not be open circuited, otherwise it will generate fatal high voltage.

Load sharing line (terminals 10, 11, 12): used for analog load distribution communication when multiple machines are connected in parallel. Terminals 10 (+), 11 (-), and 12 (shielded). The controller integrates load sharing relays internally, eliminating the need for external relays. The shielding layer should be continuously connected, but the grounding point should be carefully selected.

Output of actuator (terminals 13, 14, 15): Terminals 13 (+) and 14 (-) output 0-200mA, 4-20mA, 0-20mA or PWM signals. Terminal 15 is shielded grounding. For actuators such as EG-3P, pay attention to jumper connections.

Discrete inputs (terminals 34-41): 8 configurable switch inputs, with a common terminal of 33. It can be powered by external 24V or 24V provided internally by the controller (terminals 31-32, maximum 100mA). Default logic: Terminal 34 (Close to Run) is closed to allow fuel control; Terminals 35-37 can be configured for reset, external shutdown, idle/rated switching, CB auxiliary contacts, etc; Terminal 38 (speed/load increase), 39 (speed/load decrease), 40 (load), 41 (base load).

Discrete output (terminals 42-48): 4 low side drive outputs (DO1-DO4), maximum 200mA, requiring external 12/24V power supply (terminals 42+, 43-). Can be configured as shutdown indication, alarm, electronic overspeed test, circuit breaker trip command, etc. DO1 can also be used as a PWM actuator output.

Analog input (terminals 19-24): Two configurable analog inputs (4-20mA, 1-5V, or ± 2.5V). Terminals 19-21 are AI1, and 22-24 are AI2. Function options: remote speed set point, base load set point, synchronous input, MAP limiter input, external load sensor.

Analog output (terminals 16, 17, 18): 4-20mA output, configurable for engine speed, speed reference, fuel demand, load percentage, etc.

3. Installation checklist

Before powering on, it is essential to complete the following checks:

The actuator connecting rod is not loose or stuck, and the engine fuel rack should be completely closed when the actuator is in the minimum fuel position.

The clearance between speed sensors is 0.25-1.0 mm, and the gear ring diameter jump is less than 0.5 mm.

All shielded wires are grounded at a single point at the controller end.

The power polarity is correct, and the voltage is between 18-36V.


Software configuration: Use Control Assistant or Toolkit Service Tool

The configuration of 2301E is completely completed through computer software. Woodward offers two options: Control Assistant (recommended, graphical interface) and 2301E Toolkit Service Tool (more traditional menu style). Both need to be connected to the RS-232 port of the controller through a null modem cable, with a default baud rate of 115200.

First configuration of key parameters (configuration menu):

Rated speed (A menu): Enter the synchronous speed corresponding to 60Hz or 50Hz (such as 1800rpm/1500rpm).

Gear teeth (B menu): The number of teeth on the flywheel ring gear or speed measuring gear. It is necessary to ensure that the MPU frequency is less than 25000 Hz at the highest speed, and it is recommended to be less than 19000 Hz.

Speed sensing type (B menu): Usually choose 1 (medium high speed engine, sampling average every 1/16 revolutions) or 5 (adaptive filtering, recommended for engines with torsional vibration).

Type of actuator (F menu): Select the output range (0-200mA as default) and whether to reverse acting. When the reverse acting actuator loses power, fully open the fuel and cooperate with the mechanical backup governor.

Discrete input function (C menu): Assign functions to terminals 35-37. Commonly used: reset, idle/rated, CB assist (equal/droop switching).

Discrete output function (D menu): Assign DO1-DO4 functions. Commonly used: shutdown, alarm, circuit breaker trip command.

Analog input function (E menu): Assign functions for AI1 and AI2. Note that the two cannot be repeated.

After completing the configuration, the controller must be placed in I/O Lock mode (via software icon), at which point the engine must be shut down and all outputs must be zero. After configuring the application, use Reset to restart the controller and save the values to EEPROM, otherwise the configuration will be lost after power failure.

Detailed explanation of core control functions

The 2301E integrates a complete engine generator control logic, with the following most commonly used functions:

1. Speed control and PID dynamics

Prop Gain: determines the strength of the response to velocity error. Divided into idle gain and rated gain, with linear interpolation between the two.

Reset: Integrate time to eliminate steady-state velocity errors. The smaller the reset value (the larger the time constant), the weaker the integration effect.

Actor Compensation: Differential/leading action that compensates for the inertia of the actuator and fuel system.

Window Width and Gain Ratio: When the velocity error exceeds the window width, the gain is automatically multiplied by the gain ratio, achieving excellent performance of "steady-state low gain, transient high gain".

5-point gain map: suitable for non-linear gas engines (such as butterfly valves), set the gain in segments according to the load (fuel demand%), and linearize the system response.

2. Fuel limiter

Start Fuel Limit: Limit the maximum fuel consumption during the start-up process to prevent black smoke or overshoot. Start Ramp Rate can be set.

Max Fuel Limit: Absolute fuel limit, equivalent to electronic rack limit.

Idle Fuel Limiter: Only effective in idle state, used to prevent "cylinder flooding" when starting a gas engine.

Torque limiter: A multi-stage fuel restriction based on engine speed to protect the mechanical components of the engine.

MAP Limiter: Fuel restriction based on intake pressure to prevent over injection when boost pressure is insufficient.

3. Load control mode

Droop mode: suitable for parallel connection with an infinite power grid. When the load increases, the speed decreases linearly, and the percentage of droop can be adjusted (typically 3-5%). Load detection is based on the actual power (kW) calculated by PT/CT.

Isochronous mode: suitable for single machine islanding or parallel connection with multiple machines through load sharing lines. The speed remains constant, and the load is distributed proportionally according to its capacity.

Base Load Mode: When connected in parallel with the power grid, the controller outputs constant active power according to the set value, with the frequency determined by the power grid. The base load setting value can be remotely adjusted through the up/down switch or analog signal.

4. Soft loading and unloading

When the generator circuit breaker is closed and the 'load' input is closed, the controller smoothly increases the load from no load to the target value (equal time sharing or base load) according to the set loading rate (kW/sec). When unloading, reduce the unloading rate to the Unload Trip Level and wait for an adjustable time before issuing a Breaker Open Command. This function avoids the impact of sudden load changes on the power grid and engine.

5. Load Pulse/Load Rejection

This is a major highlight feature of 2301E. By detecting the rate of change of the generator load (dP/dt), the controller performs an instantaneous compensation on the fuel actuator in advance when the engine speed has not changed significantly:

Load Pulse: When a rapid increase in load is detected (such as when a large motor starts), the controller briefly increases fuel output to compensate for the upcoming speed drop.

Load Rejection: When a rapid decrease in load is detected (such as a circuit breaker tripping), the controller briefly reduces fuel output to prevent overspeed.

Generator Breaker Open Pulse: When the circuit breaker is disconnected and the current load is higher than the set value, the fuel instantly drops to zero for a period of time, effectively suppressing the speed rise after load shedding.


Dynamic tuning practice: from start-up to optimization

The goal of dynamic tuning is to find the PID parameters that make the engine stable and respond the fastest. Recommended on-site tuning process based on Zeigler Nichols method:

Preparation steps:

Ensure that the engine is able to run steadily at idle speed. Copy the first set of dynamic parameters to the second set for quick switching in case of instability.

Use the Trend Tool of Control Assistant or analog output (4-20mA corresponding to speed) to record the speed response curve.

Setting steps:

Proportional control only: Set Reset to 0.01 (minimum integral action) and actuator compensation to 0.01 (minimum differential action). Set the window width to 60rpm, the gain ratio to 1.0, and the gain slope to 0.

Find the critical gain Ku: Gradually increase the proportional gain (first adjust the idle gain, then adjust the rated gain), and use the "actuator bump" function (set the bump amplitude to 1-2% in the O menu for 0.1 seconds) to excite the system after each increase. Observe the speed oscillation. Continuously increase the gain until an equal amplitude oscillation (critical stability) occurs, and record the gain value Ku at this time.

Measurement of oscillation period Pu: Measure the time (in seconds) of a complete oscillation period from the trend chart, denoted as Pu.

Calculate initial PID:

Final gain=Ku/1.7

Reset=2/Pu (e.g. when Pu=3.133 seconds, reset ≈ 0.64)

Actuator compensation=Pu/8 (e.g. 3.133/8 ≈ 0.39)

Fine tuning: After entering the calculated value, perform a load step test again (such as adding/subtracting 20% load). If the speed overshoot is too large, increase the reset appropriately (reduce the integration time) or decrease the gain. If the recovery is too slow, reduce the reset.

Adjust the window width to gain ratio: Set the gain ratio to 2.0, then gradually decrease the window width (from 60rpm downwards, decreasing by 10rpm each time), while observing the load step response. When the window width is small enough to cause instability, increase it back to the previous stable value. This function can significantly reduce the speed drop during load transients.

For nonlinear systems such as gas engines, 5-point gain mapping is required. The method is to find stable gains at different load points (unloaded, 25%, 50%, 75%, 100%), and then fill in the corresponding breakpoints and gain values.

Practical troubleshooting: common problems and solutions

The following are typical faults and troubleshooting paths based on the manual and on-site experience summary:

Fault 1: Engine cannot start, actuator does not operate

Check power supply: Is the voltage between terminals 48-49 ≥ 18V? Is the CPU status LED green (if red, it indicates I/O Lock or self-test failure)?

Check speed signal: When starting, is the AC voltage between terminals 25-26 ≥ 1.0Vrms? If it is 0, check the resistance value (about 100-300 Ω) and gap of the MPU.

Check the Start Fuel Limit: Check the Fuel Demand% in the Display Menu. Does it jump to the Start Fuel Limit setting (such as 100%) when starting? If it remains at 0, it may be because the "Close to Run" input (terminal 34) is not closed or the logic is reversed.

Check the coverage of the failed speed signal: If the protection is triggered due to the absence of MPU signal during startup, the discrete input configured as "Failed Speed Override" can be temporarily closed to allow startup.

Fault 2: Engine instability (traveling block)

Fast jitter (>1Hz): The proportional gain is too high. Reduce Rated Prop Gain.

Slow oscillation (<0.5Hz): The reset is too strong (the value is too large). Reduce the Reset value (increase integration time).

Check actuator compensation: If the compensation is too large, the actuator will become overly active. For diesel engines, compensation is usually 0.1-0.2; For carburetor gas engines, 0.3-0.5.

Check speed filter: If there is strong ignition torsional vibration in the engine, the speed filter frequency can be reduced (default 12Hz, adjustable to 8-10Hz).

Fault 3: Uneven load distribution during parallel connection

Check CT/PT phase: Use the "Phase Correction Procedure" in the manual. The most common problem is CT polarity reversal or phase sequence error. Correction can be achieved by temporarily swapping CT terminals and observing load readings.

Calibrate load reading: In Service Menu T, use "KW Input Calibration" to adjust the zero point and gain so that the Generator Out (kW) displayed on the controller is consistent with the external instrument.

Check load share gain: If the load of a certain unit fluctuates greatly, its load share gain can be appropriately reduced.

Check for equal/droop switching: Confirm that the CB Aux discrete input (terminal 37) is true after the circuit breaker is closed, and the controller enters equal time mode. Otherwise, it will be in a drooping mode and unable to be evenly distributed.

Fault 4: Overspeed after load shedding

Enable circuit breaker trip pulse: In Service Menu W, set ENABLE CB LOAD REJECTION=TRUE and set GEN REJ LOAD LEVEL (e.g. 60%) and GEN REJ PULSE TIME (e.g. 0.2 seconds). In this way, when the circuit breaker is disconnected and the load is greater than 60%, the fuel will instantly return to zero for 0.2 seconds.

Check the load rejection function: Set ENABLE LOAD REJECT FUNCT to TRUE and adjust the LOAD REJECT DERIV and LD REJECT MULT ACT parameters.

Fault 5: Unable to establish Modbus communication

Confirm port settings: Use RS-422 port (terminal X2) and set the correct baud rate (default 115200), data bit (8), stop bit (1), and no checksum in Service Menu Z.

Check the address: PORT 2 Address defaults to 1 to ensure that the primary access address matches.

Enable Modbus Control (if writing is required): Set ENABLE MODBUS Control to TRUE.

Wiring: RS-422 is a differential pair (T+, T -, R+, R -), pay attention to cross connecting with the main station.


Modbus Communication and Monitoring

The RS-422 port of 2301E supports Modbus RTU protocol and can communicate with DCS or HMI as a slave. The commonly supported function codes include:

01: Reading coil (digital output status)

02: Read discrete input (switch status)

03: Read and hold register (analog output)

04: Read input register (analog input, such as speed, load)

05: Writing a single coil

06: Write single register

16: Write multiple registers

Key Modbus addresses (partial):

0:0002: Run command (latch)

0:0003: Shutdown command

0:0006: Rated speed selection

0:0010: Isochronous mode

3: 0003: Engine RPM

3: 0005: Generator load (kW)

4: 0002: Remote speed setting value (needs to be multiplied by 10 to improve resolution)

Note: When using Modbus control, discrete inputs remain valid (OR logic). It is recommended to design heartbeat timeout protection in the program. When communication is interrupted, the controller can maintain the last value or lower it to the lower limit according to the configuration (REMOTE SPD LOCK IN Last).


Maintenance and Service Options

Woodward provides complete lifecycle support for 2301E:

Replacement/Exchange Service (24 hours): In the event of a malfunction, replacement units can be quickly obtained to reduce downtime.

Flat Rate Repair: Fixed price repair.

Technical assistance: can be provided through EngineHelpDesk@Woodward.com Contact or dial the Global Service Center phone number.

Firmware upgrade: Use Control Assistant or Toolkit Service Tool to upgrade application software (such as from 5418-6350 to higher versions). Appendix D lists the modifications made in each version, such as the addition of precise frequency control and circuit breaker tripping pulses.

Steps for replacing the controller (migrating from 2301D to 2301E):

Use Control Assistant to upload configuration files (. tc) from old 2301D.

Connect 2301E and enter I/O Lock.

Send the. tc file to 2301E. Due to software differences, approximately 35 parameters may not be automatically loaded and need to be manually inputted against the original file.

Save and restart the controller.

  • ENOTEC OXITEC 5000 SME-53310000 Oxygen Analyzer
  • SIGMATEK Krauss Maffei PC301-K 01-310-301-K Industrial PC
  • SIGMATEK SDD310-23 VARAN Servo Drive
  • SIGMATEK CDM 163 and CIC 011 C-DIAS Input Modules
  • SIGMATEK MDP 101-1 Power Module
  • SIGMATEK CM5V020 Wiring Circuit with CTMS020
  • SIGMATEK CCP521 C-DIAS Processor Module
  • SIGMATEK MDP 101-K Power Module
  • SIGMATEK ETEK C-IPC 733MHz VIA Eden 7000
  • SIGMATEK DCP 643 DIAS PLC CPU Module
  • SIGMATEK TAE121 12-200-121 Operator Terminal
  • Sigmatek TMS012-T Injection Moulding Technology Module
  • Sigmatek MDD 121-1 Controller
  • Sigmatek CDM167 Module
  • Sigmatek DCP082 DIAS Central Unit
  • Sigmatek ETT731 Built-In Terminal Touch
  • Sigmatek CCP521 C-DIAS Processor Module
  • Sigmatek Krauss Maffei PC301-K Control Cabinet PC
  • Sigmatek CIC-21 C-DIAS CAN Module
  • Sigmatek CIO-011 Multi I O Module
  • Sigmatek 01-450-152D C-IPC 152 Industrial PC
  • SIGMATEK 01-450-024 C-IPC 128MB VIA 733MHz
  • SIGMATEK CCL-081 C-DIAS Processor Module
  • SIGMATEK CP311 20-004-311 Module
  • SIGMATEK EP00000262 SLIDES MIDI I O-V3 Controller
  • SIGMATEK TMS012-T Slides Technology Module
  • SIGMATEK MDD111-1 Drive Axis Module
  • SIGMATEK MDP101-1 PLC Module
  • SIGMATEK CP111 S-DIAS Processor Module
  • DEMAG ErgoControl Sigmatek NC4 Display Unit
  • SIGMATEK DCP642 Module
  • Sigmatek Demag NC4 9617.067.03 Control Module
  • Sigmatek DCP 643 Central Processing Unit
  • Sigmatek VI 021 S-SLIDES VARAN Interface Module
  • Sigmatek SDD340-46 Servo Drive 14kVA
  • Sigmatek DSI021 Slide Siemens Interface
  • Sigmatek CCL912 C-SLIDES CPU PSU Module
  • Sigmatek ETV1521 VARAN Control Panel
  • Sigmatek ET322 Operator LCD Terminal
  • Sigmatek MDD1111 DIAS Drive Module
  • Sigmatek CAM123 Module
  • SIGMATEK CP111 VARAN Ethernet Controller
  • SigmaTek MDD 111 Axle Module
  • SIGMATEK CIO013 C-DIAS I O Module
  • SIGMATEK AKM52K-ANC2GBB0 Servomotor 640VDC
  • SIGMATEK ETT321 01-230-321 Touch Screen
  • SIGMATEK NC4Kompakt 01-250-010-D Safety Controller
  • SIGMATEK CIO011 C-DIAS Multi I O Module
  • SIGMATEK MDD 121-1 Drive Axis Module
  • SIGMATEK CDM163 Control Module
  • Sigma-Tek 4000HR-3 Heading Reference Directional Gyro
  • Sigmatek DIAS DAI 883 Analog Input Module
  • Sigmatek 0332.554.03 Printed Circuit Board Card
  • Sigma Tek 5000B-36 Attitude Gyro 8130
  • Demag NC4 0332.554.03 Sigmatek Control Board
  • Sigmatek IPC Pentium 300 CF Industrial PC
  • Sigmatek MDP 102 PLC Module
  • Sigmatek DTO163 Digital Output Module
  • Sigmatek PCT151 Touch IPC 15 Panel and I-PC C300
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SCP011 S-DIAS Safety CPU Module
  • Sigmatek SE051 Network Splitter Module
  • Sigmatek CIO011 C-DIAS I O Module
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek CCL911 CD Processor Module
  • Sigmatek SDD310-4 DIAS Drive 14kVA
  • Sigmatek CTMS020 C-DIAS Technology Module
  • Sigmatek CTMS020 CD Technology Module
  • Sigmatek CTO167 C-SLIDES Digital Output Module
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek SDD310-4 SLIDES Drive 310
  • SIGMATEK MDP 102-1 DIAS Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU Industrial
  • SIGMATEK CAO081 Analog Output Module
  • SIGMATEK DCC080L Control Module
  • SIGMATEK MDP101-1 Power Module
  • SIGMATEK SCP111 S-DIAS Safety CPU
  • SIGMATEK PC325-K Industrial PC
  • SIGMATEK ETT 731 Operator Terminal
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK 12-780-012 R8-IPC Industrial Computer
  • Sigmatek SE051 Ethernet Splitter
  • Sigmatek DAI 883 DIAS Analog Module
  • Sigma Tek 4000B-30 Directional Gyro
  • Sigmatek CP112 S-DIAS Processor Module
  • Sigmatek SDD310 DIAS Drive
  • Sigmatek SDD120-23 DIAS Drive 14kVA
  • Sigmatek C-IPC 152 Industrial PC
  • Sigmatek CIV513 VARAN Control Module
  • Sigmatek DCP 082 Processor Module
  • Sigmatek C-IPC Industrial PC 01-450-023 GEB
  • SIGMATEK PC572 Operating Terminal
  • SIGMATEK DCC041 DIAS Compact Controller HW 6.10
  • SIGMATEK C-IPC 152 1GB Celeron M440 Controller
  • SIGMATEK 01-310-322-K PC322-K Industrial PC
  • SIGMATEK TAE732-P Touch Screen Operator Panel
  • SIGMATEK 01-018-100 Control Module
  • SIGMATEK DDI-164 Digital Input Module
  • Sigma-Tek 5000B-36 Artificial Horizon
  • SIGMATEK 12-780-012 R8-IPC Geode LX800 Computer
  • SIGMATEK CTMS 020 Servo Drive
  • Sigmatek MDD121-1 Controller
  • Sigmatek ETV1021-L VARAN Terminal
  • Sigmatek DST022 DIAS Module
  • Sigmatek CCP512-K C-Dias Processor Module
  • Sigmatek SRO 021 Relay Output Module
  • Sigmatek SDI 101 Digital Input Module
  • Sigmatek IPC 221 Industrial PC
  • Sigmatek DNC-305 Digital Input Module
  • Sigmatek SDD335 DIAS Drive
  • Sigmatek C-IPC Industrial Controller
  • SIGMATEK 01-450-031 C-IPC 256MB LX800 Computer
  • SIGMATEK SDD310-3 DIAS Drive 310
  • SIGMATEK DSV011 SLIDES Hub Module 05-023-011
  • SIGMATEK CNC031 CD Analog Module 12-011-031
  • SIGMATEK 01-450-031 C-IPC 256MB LX800
  • SIGMATEK 01-450-026 C-IPC VIA 733MHz Controller
  • SIGMATEK DCP-643 DIAS CPU Module with DKL-003
  • SIGMATEK MDD111-L DIAS Drive Axis Module
  • SIGMATEK SDD310-23-L DIAS Drive 310
  • SIGMATEK Viscotec ETV0551 Touch Panel
  • SIGMATEK PC321K Industrial Computer
  • SIGMATEK MDP 102-1 SLIDES Power Module
  • SIGMATEK TAE-151 12-200-151 Light Terminal
  • SIGMATEK CP102 20-004-102P6995B HMI Panel
  • SIGMATEK CAM-123 12-017-123-C Analog Mixing Module
  • SIGMATEK DCC041 DIAS Compact Controller
  • SIGMATEK DVI021 and DKL015 DIAS Power Module