WOODWARD 2301E Digital Speed Controller

F: | Au:FAN | DA:2026-04-16 | 387 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Woodward 2301E Digital Load Distribution and Speed Controller: Practical Engineering Configuration, Debugging, and Troubleshooting

In the field of generator set control, whether it is a diesel engine or a gas engine driven generator, achieving precise speed regulation and stable load distribution is the core to ensure power quality and system reliability. The Woodward 2301E digital controller is a classic product designed for this purpose. It is based on a microprocessor and not only inherits the functions of the 2301A and 2301D analog controllers, but also adds more advanced control features through software flexibility, making it an ideal choice for upgrading old control systems or building new projects.

This article will deeply analyze the hardware integration points, software configuration process, core control algorithms, dynamic tuning methods, Modbus communication settings, and systematic troubleshooting strategies of the controller based on the 2301E installation operation manual (Manual 26641) from the perspective of frontline engineering personnel. It provides a practical technical guide for engineers engaged in generator set debugging, maintenance, and modification.


Hardware installation and wiring: laying the foundation for reliable operation

There are two ordering numbers for the 2301E controller: 8273-1011 (for regular use) and 8273-1012 (for hazardous use). Both are metal chassis with a single circuit board design, connected to an external computer via a 9-pin RS-232 port for configuration.

1. Power and environmental requirements

The controller requires a DC power supply of 18 to 36 Vdc, with a typical power consumption of ≤ 20W and a maximum current of approximately 600mA. The power supply must come from a SELV (Safety Extra Low Voltage) certified power supply/battery charger. The ambient temperature range is -40 to+70 ℃, and it can be installed inside the control cabinet, but it is strictly prohibited to install it directly on the engine. For hazardous locations (Class I, Division 2, Groups A, B, C, D), the final installation enclosure must achieve IP54 protection level and meet the requirements of IEC 60079-0.

2. Key wiring terminals

Power supply (terminals 48, 49, 50): The positive terminal is connected to 48, the negative terminal is connected to 49, and 50 are optional protective grounding (PE) connection points. It is recommended to use shielded twisted pair cables for the power cord, with the shielding layer grounded at a single point on the controller end.

Speed sensor (terminals 25, 26, 27): connected to a magneto resistive speed probe (MPU). The frequency range is 100-25000 Hz, and the voltage range is 1.7-35 Vac (≥ 1.0 Vrms required for startup). Use shielded wire and connect the shielding layer to terminal 27 (chassis).

PT/CT input (terminals 1-9): The three-phase voltage (PT) is connected to terminals 1-3 (line voltage 90-120 Vac or 200-240 Vac), and the three-phase current (CT) is connected to terminals 4-9 (5A secondary side). CT burden is less than 0.1 VA/phase. Attention: The CT secondary side must not be open circuited, otherwise it will generate fatal high voltage.

Load sharing line (terminals 10, 11, 12): used for analog load distribution communication when multiple machines are connected in parallel. Terminals 10 (+), 11 (-), and 12 (shielded). The controller integrates load sharing relays internally, eliminating the need for external relays. The shielding layer should be continuously connected, but the grounding point should be carefully selected.

Output of actuator (terminals 13, 14, 15): Terminals 13 (+) and 14 (-) output 0-200mA, 4-20mA, 0-20mA or PWM signals. Terminal 15 is shielded grounding. For actuators such as EG-3P, pay attention to jumper connections.

Discrete inputs (terminals 34-41): 8 configurable switch inputs, with a common terminal of 33. It can be powered by external 24V or 24V provided internally by the controller (terminals 31-32, maximum 100mA). Default logic: Terminal 34 (Close to Run) is closed to allow fuel control; Terminals 35-37 can be configured for reset, external shutdown, idle/rated switching, CB auxiliary contacts, etc; Terminal 38 (speed/load increase), 39 (speed/load decrease), 40 (load), 41 (base load).

Discrete output (terminals 42-48): 4 low side drive outputs (DO1-DO4), maximum 200mA, requiring external 12/24V power supply (terminals 42+, 43-). Can be configured as shutdown indication, alarm, electronic overspeed test, circuit breaker trip command, etc. DO1 can also be used as a PWM actuator output.

Analog input (terminals 19-24): Two configurable analog inputs (4-20mA, 1-5V, or ± 2.5V). Terminals 19-21 are AI1, and 22-24 are AI2. Function options: remote speed set point, base load set point, synchronous input, MAP limiter input, external load sensor.

Analog output (terminals 16, 17, 18): 4-20mA output, configurable for engine speed, speed reference, fuel demand, load percentage, etc.

3. Installation checklist

Before powering on, it is essential to complete the following checks:

The actuator connecting rod is not loose or stuck, and the engine fuel rack should be completely closed when the actuator is in the minimum fuel position.

The clearance between speed sensors is 0.25-1.0 mm, and the gear ring diameter jump is less than 0.5 mm.

All shielded wires are grounded at a single point at the controller end.

The power polarity is correct, and the voltage is between 18-36V.


Software configuration: Use Control Assistant or Toolkit Service Tool

The configuration of 2301E is completely completed through computer software. Woodward offers two options: Control Assistant (recommended, graphical interface) and 2301E Toolkit Service Tool (more traditional menu style). Both need to be connected to the RS-232 port of the controller through a null modem cable, with a default baud rate of 115200.

First configuration of key parameters (configuration menu):

Rated speed (A menu): Enter the synchronous speed corresponding to 60Hz or 50Hz (such as 1800rpm/1500rpm).

Gear teeth (B menu): The number of teeth on the flywheel ring gear or speed measuring gear. It is necessary to ensure that the MPU frequency is less than 25000 Hz at the highest speed, and it is recommended to be less than 19000 Hz.

Speed sensing type (B menu): Usually choose 1 (medium high speed engine, sampling average every 1/16 revolutions) or 5 (adaptive filtering, recommended for engines with torsional vibration).

Type of actuator (F menu): Select the output range (0-200mA as default) and whether to reverse acting. When the reverse acting actuator loses power, fully open the fuel and cooperate with the mechanical backup governor.

Discrete input function (C menu): Assign functions to terminals 35-37. Commonly used: reset, idle/rated, CB assist (equal/droop switching).

Discrete output function (D menu): Assign DO1-DO4 functions. Commonly used: shutdown, alarm, circuit breaker trip command.

Analog input function (E menu): Assign functions for AI1 and AI2. Note that the two cannot be repeated.

After completing the configuration, the controller must be placed in I/O Lock mode (via software icon), at which point the engine must be shut down and all outputs must be zero. After configuring the application, use Reset to restart the controller and save the values to EEPROM, otherwise the configuration will be lost after power failure.

Detailed explanation of core control functions

The 2301E integrates a complete engine generator control logic, with the following most commonly used functions:

1. Speed control and PID dynamics

Prop Gain: determines the strength of the response to velocity error. Divided into idle gain and rated gain, with linear interpolation between the two.

Reset: Integrate time to eliminate steady-state velocity errors. The smaller the reset value (the larger the time constant), the weaker the integration effect.

Actor Compensation: Differential/leading action that compensates for the inertia of the actuator and fuel system.

Window Width and Gain Ratio: When the velocity error exceeds the window width, the gain is automatically multiplied by the gain ratio, achieving excellent performance of "steady-state low gain, transient high gain".

5-point gain map: suitable for non-linear gas engines (such as butterfly valves), set the gain in segments according to the load (fuel demand%), and linearize the system response.

2. Fuel limiter

Start Fuel Limit: Limit the maximum fuel consumption during the start-up process to prevent black smoke or overshoot. Start Ramp Rate can be set.

Max Fuel Limit: Absolute fuel limit, equivalent to electronic rack limit.

Idle Fuel Limiter: Only effective in idle state, used to prevent "cylinder flooding" when starting a gas engine.

Torque limiter: A multi-stage fuel restriction based on engine speed to protect the mechanical components of the engine.

MAP Limiter: Fuel restriction based on intake pressure to prevent over injection when boost pressure is insufficient.

3. Load control mode

Droop mode: suitable for parallel connection with an infinite power grid. When the load increases, the speed decreases linearly, and the percentage of droop can be adjusted (typically 3-5%). Load detection is based on the actual power (kW) calculated by PT/CT.

Isochronous mode: suitable for single machine islanding or parallel connection with multiple machines through load sharing lines. The speed remains constant, and the load is distributed proportionally according to its capacity.

Base Load Mode: When connected in parallel with the power grid, the controller outputs constant active power according to the set value, with the frequency determined by the power grid. The base load setting value can be remotely adjusted through the up/down switch or analog signal.

4. Soft loading and unloading

When the generator circuit breaker is closed and the 'load' input is closed, the controller smoothly increases the load from no load to the target value (equal time sharing or base load) according to the set loading rate (kW/sec). When unloading, reduce the unloading rate to the Unload Trip Level and wait for an adjustable time before issuing a Breaker Open Command. This function avoids the impact of sudden load changes on the power grid and engine.

5. Load Pulse/Load Rejection

This is a major highlight feature of 2301E. By detecting the rate of change of the generator load (dP/dt), the controller performs an instantaneous compensation on the fuel actuator in advance when the engine speed has not changed significantly:

Load Pulse: When a rapid increase in load is detected (such as when a large motor starts), the controller briefly increases fuel output to compensate for the upcoming speed drop.

Load Rejection: When a rapid decrease in load is detected (such as a circuit breaker tripping), the controller briefly reduces fuel output to prevent overspeed.

Generator Breaker Open Pulse: When the circuit breaker is disconnected and the current load is higher than the set value, the fuel instantly drops to zero for a period of time, effectively suppressing the speed rise after load shedding.


Dynamic tuning practice: from start-up to optimization

The goal of dynamic tuning is to find the PID parameters that make the engine stable and respond the fastest. Recommended on-site tuning process based on Zeigler Nichols method:

Preparation steps:

Ensure that the engine is able to run steadily at idle speed. Copy the first set of dynamic parameters to the second set for quick switching in case of instability.

Use the Trend Tool of Control Assistant or analog output (4-20mA corresponding to speed) to record the speed response curve.

Setting steps:

Proportional control only: Set Reset to 0.01 (minimum integral action) and actuator compensation to 0.01 (minimum differential action). Set the window width to 60rpm, the gain ratio to 1.0, and the gain slope to 0.

Find the critical gain Ku: Gradually increase the proportional gain (first adjust the idle gain, then adjust the rated gain), and use the "actuator bump" function (set the bump amplitude to 1-2% in the O menu for 0.1 seconds) to excite the system after each increase. Observe the speed oscillation. Continuously increase the gain until an equal amplitude oscillation (critical stability) occurs, and record the gain value Ku at this time.

Measurement of oscillation period Pu: Measure the time (in seconds) of a complete oscillation period from the trend chart, denoted as Pu.

Calculate initial PID:

Final gain=Ku/1.7

Reset=2/Pu (e.g. when Pu=3.133 seconds, reset ≈ 0.64)

Actuator compensation=Pu/8 (e.g. 3.133/8 ≈ 0.39)

Fine tuning: After entering the calculated value, perform a load step test again (such as adding/subtracting 20% load). If the speed overshoot is too large, increase the reset appropriately (reduce the integration time) or decrease the gain. If the recovery is too slow, reduce the reset.

Adjust the window width to gain ratio: Set the gain ratio to 2.0, then gradually decrease the window width (from 60rpm downwards, decreasing by 10rpm each time), while observing the load step response. When the window width is small enough to cause instability, increase it back to the previous stable value. This function can significantly reduce the speed drop during load transients.

For nonlinear systems such as gas engines, 5-point gain mapping is required. The method is to find stable gains at different load points (unloaded, 25%, 50%, 75%, 100%), and then fill in the corresponding breakpoints and gain values.

Practical troubleshooting: common problems and solutions

The following are typical faults and troubleshooting paths based on the manual and on-site experience summary:

Fault 1: Engine cannot start, actuator does not operate

Check power supply: Is the voltage between terminals 48-49 ≥ 18V? Is the CPU status LED green (if red, it indicates I/O Lock or self-test failure)?

Check speed signal: When starting, is the AC voltage between terminals 25-26 ≥ 1.0Vrms? If it is 0, check the resistance value (about 100-300 Ω) and gap of the MPU.

Check the Start Fuel Limit: Check the Fuel Demand% in the Display Menu. Does it jump to the Start Fuel Limit setting (such as 100%) when starting? If it remains at 0, it may be because the "Close to Run" input (terminal 34) is not closed or the logic is reversed.

Check the coverage of the failed speed signal: If the protection is triggered due to the absence of MPU signal during startup, the discrete input configured as "Failed Speed Override" can be temporarily closed to allow startup.

Fault 2: Engine instability (traveling block)

Fast jitter (>1Hz): The proportional gain is too high. Reduce Rated Prop Gain.

Slow oscillation (<0.5Hz): The reset is too strong (the value is too large). Reduce the Reset value (increase integration time).

Check actuator compensation: If the compensation is too large, the actuator will become overly active. For diesel engines, compensation is usually 0.1-0.2; For carburetor gas engines, 0.3-0.5.

Check speed filter: If there is strong ignition torsional vibration in the engine, the speed filter frequency can be reduced (default 12Hz, adjustable to 8-10Hz).

Fault 3: Uneven load distribution during parallel connection

Check CT/PT phase: Use the "Phase Correction Procedure" in the manual. The most common problem is CT polarity reversal or phase sequence error. Correction can be achieved by temporarily swapping CT terminals and observing load readings.

Calibrate load reading: In Service Menu T, use "KW Input Calibration" to adjust the zero point and gain so that the Generator Out (kW) displayed on the controller is consistent with the external instrument.

Check load share gain: If the load of a certain unit fluctuates greatly, its load share gain can be appropriately reduced.

Check for equal/droop switching: Confirm that the CB Aux discrete input (terminal 37) is true after the circuit breaker is closed, and the controller enters equal time mode. Otherwise, it will be in a drooping mode and unable to be evenly distributed.

Fault 4: Overspeed after load shedding

Enable circuit breaker trip pulse: In Service Menu W, set ENABLE CB LOAD REJECTION=TRUE and set GEN REJ LOAD LEVEL (e.g. 60%) and GEN REJ PULSE TIME (e.g. 0.2 seconds). In this way, when the circuit breaker is disconnected and the load is greater than 60%, the fuel will instantly return to zero for 0.2 seconds.

Check the load rejection function: Set ENABLE LOAD REJECT FUNCT to TRUE and adjust the LOAD REJECT DERIV and LD REJECT MULT ACT parameters.

Fault 5: Unable to establish Modbus communication

Confirm port settings: Use RS-422 port (terminal X2) and set the correct baud rate (default 115200), data bit (8), stop bit (1), and no checksum in Service Menu Z.

Check the address: PORT 2 Address defaults to 1 to ensure that the primary access address matches.

Enable Modbus Control (if writing is required): Set ENABLE MODBUS Control to TRUE.

Wiring: RS-422 is a differential pair (T+, T -, R+, R -), pay attention to cross connecting with the main station.


Modbus Communication and Monitoring

The RS-422 port of 2301E supports Modbus RTU protocol and can communicate with DCS or HMI as a slave. The commonly supported function codes include:

01: Reading coil (digital output status)

02: Read discrete input (switch status)

03: Read and hold register (analog output)

04: Read input register (analog input, such as speed, load)

05: Writing a single coil

06: Write single register

16: Write multiple registers

Key Modbus addresses (partial):

0:0002: Run command (latch)

0:0003: Shutdown command

0:0006: Rated speed selection

0:0010: Isochronous mode

3: 0003: Engine RPM

3: 0005: Generator load (kW)

4: 0002: Remote speed setting value (needs to be multiplied by 10 to improve resolution)

Note: When using Modbus control, discrete inputs remain valid (OR logic). It is recommended to design heartbeat timeout protection in the program. When communication is interrupted, the controller can maintain the last value or lower it to the lower limit according to the configuration (REMOTE SPD LOCK IN Last).


Maintenance and Service Options

Woodward provides complete lifecycle support for 2301E:

Replacement/Exchange Service (24 hours): In the event of a malfunction, replacement units can be quickly obtained to reduce downtime.

Flat Rate Repair: Fixed price repair.

Technical assistance: can be provided through EngineHelpDesk@Woodward.com Contact or dial the Global Service Center phone number.

Firmware upgrade: Use Control Assistant or Toolkit Service Tool to upgrade application software (such as from 5418-6350 to higher versions). Appendix D lists the modifications made in each version, such as the addition of precise frequency control and circuit breaker tripping pulses.

Steps for replacing the controller (migrating from 2301D to 2301E):

Use Control Assistant to upload configuration files (. tc) from old 2301D.

Connect 2301E and enter I/O Lock.

Send the. tc file to 2301E. Due to software differences, approximately 35 parameters may not be automatically loaded and need to be manually inputted against the original file.

Save and restart the controller.

  • LTi SO84.450 Servo Drive Controller - 450A Three-Phase BG7
  • LTi SO84.375 Servo Drive Controller - 375A Three-Phase BG7
  • LTi SO84.325 Servo Drive Controller - 325A Three-Phase BG7
  • LTi SO84.250 Servo Drive Controller - 250A Three-Phase BG7
  • LTi SO84.170 Servo Drive Controller - 170A Three-Phase BG6a
  • LTi SO84.143 Servo Drive Controller - 143A Three-Phase BG6a
  • LTi SO84.110 Servo Drive Controller - 110A Three-Phase BG6
  • LTi SO84.090 Servo Drive Controller - 90A Three-Phase BG6
  • LTi SO84.072 Servo Drive Controller - 72A Three-Phase BG5
  • LTi SO84.060 Servo Drive Controller - 60A Three-Phase BG5
  • LTi SO84.045 Servo Drive Controller - 45A Three-Phase BG5
  • LTi SO84.032 Servo Drive Controller - 32A Three-Phase BG4
  • LTi SO84.024 Servo Drive Controller - 24A Three-Phase BG4
  • LTi SO84.020 Servo Drive Controller - 20A Three-Phase BG3
  • LTi SO84.016 Servo Drive Controller - 16A Three-Phase BG3
  • LTi SO84.012 Servo Drive Controller - 12A Three-Phase BG2
  • LTi SO84.008 Servo Drive Controller - 8A Three-Phase BG2
  • LTi SO84.006 Servo Drive Controller - Three-Phase 230-480V 6A
  • LTi SO84.004 Servo Drive Controller - Three-Phase 230-480V 4A
  • LTi SO82.004 Servo Drive Controller - Single-Phase 230V 4A
  • HMS Anybus AB7646-F Gateway Manual
  • Schneider ATV930D75N4 Inverter Manual
  • Mitsubishi Q2ASHCPU-S1 System Manual
  • Fanuc A20B-3300-0319 Board Specification
  • Mitsubishi QD60P8-G Counter Module Guide
  • Nidec Unidrive M701 Inverter Manual
  • ABB AO895 Analog Output Module Guide
  • Mitsubishi Q2ASHCPU Controller System Manual
  • ABB Pluto S20 v2 Safety PLC Manual
  • Omron CJ1W-NC413 Position Module Manual
  • B&R X20AI4632 Analog Input Module 4 Channel
  • OMRON CS1G-CPU44H Ver. 4.1 CPU Unit PLC
  • Beckhoff EL2911-2200 TwinSAFE Logic Terminal for EtherCAT
  • Mitsubishi 2D-TZ368 Parallel I/O Interface Card
  • Mitsubishi A3ACPU PLC CPU Module for MELSEC A Series
  • Mitsubishi NF630-SEW 4P Adjustable Circuit Breaker 300-630A
  • Keyence XG-8700L Multi-camera Vision System for Inspection
  • Beckhoff C6017-0010 Ultra Compact Industrial PC
  • B&R 3AT660.6 PLC Module from Automation Panel Series
  • GE F31X300CCHALG2 PC Board with 531X133PRUAPG1 Card
  • STMicroelectronics STM32L100R8T6ATR MCU Arm Cortex-M3
  • Omron CS1W-CLK13 Controller Link Unit
  • Schneider BMENOC0301 Ethernet Communication Module
  • HELUKABEL Braids PLC-30 40 E2UK Braided Cable Sleeve
  • Pe323 h0102de323a0 PLC I/O Module
  • Mitsubishi GT2512-STBA GT2512-STBD HMI 12.1 Inch Touch Screen
  • Samsung LTM213UP01 21.3 Inch LCD Monitor Panel
  • Allen-Bradley 440R-W23219 Guardmaster Safety Relay
  • Beckhoff EL2535 EtherCAT Terminal PWM Output
  • HELUKABEL Braids PLC-40 55 E2UK Braided Cable Sleeve
  • Allen Bradley 1769-OB16 16-Point Sourcing Output Module
  • Balluff BES 516-604-DZ-3 Delay Safety Relay for Industrial Timing
  • Siemens 6GK7542-1AX10-0XE0 PROFIBUS Communication Module for S7-1500
  • GE IC693BEM340 FIP Controller for Series 90-30 PLC
  • OMRON C200HG-CPU63-E Programmable Logic Controller CPU Unit
  • Schneider EOCR-PMZ Relay Manual
  • Honeywell C36TC0UA21D0 Controller Specifications
  • Emerson Ovation VE4001S2T2B4 Input Module
  • Omron CJ1M-CPU22 CPU Specifications
  • Grundig NEA02 AES 0 Card Specifications
  • Omron CJ1W-AD081-V1 Analog Input Specifications
  • IDEC FS1A-C21S Safety Controller Manual
  • IFM O3D303 Smart 3D Sensor Specifications
  • Siemens 6SN1123-1AB00-0BA2 Power Module Guide
  • B&R 4PP035.0300-01 Power Panel Manual
  • Siemens 6ES7 153-2BA10-0XB0 IM Module
  • Beckhoff EL3356-0010 Analog Input Module
  • Siemens 3RW4037-1BB04 Soft Starter
  • Lenze EVF8216-E VFD
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI
  • Allen-Bradley 1764-28BXB PLC MicroLogix 1500
  • SP-RDM2 Relay Module Dual Reader Interface
  • Keyence GC-S84 Programmable Safety Controller
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI 10.4 Inch
  • Eurotherm MINI8 PLC Temperature Controller
  • Mitsubishi GT2512-STBA GT2512-STBD HMI 12.1 Inch
  • ABB ACS380-040S-02A6-4 VFD 0.75kW 480V
  • Dage PC514 ISSUE A PLC O.P.I Board
  • ROBICON 460T46.01 REV C Printed Circuit Board
  • Omron NX502-1300 Controller Unit NX5 CPU
  • B&R X20CM0985 PLC Module
  • Banner XS26-2DE 85064 Safety Controller
  • Siemens 3SK2122-1AA10 Safety Relay
  • HMS Anybus AB7646-F Gateway PROFIBUS EtherNet/IP
  • Siemens 6SN1118-0DM11-0AA0 SIMODRIVE 611 Card
  • Siemens C98043-A7001-L2-4 CUD1 Control Board
  • Stein Sohn E 083.1 PLC Rack Module 0010026-054100A
  • Allen Bradley 800H-2HA7P Push Button Station
  • Schneider BMXNRP0200 M340 PLC Module
  • KEPCO BOP 200-1M Bipolar Power Supply Amplifier
  • Mitsubishi Q2ASHCPU PLC Module with A1SX42 A1SY42 QC24-R2 A1SD75P2-S3
  • Siemens Siprotec 7SJ61 Overcurrent Protection
  • Keyence LJ-V7000 Controller Laser Profiler
  • Siemens 6EP3437-8SB00-0AY0 Power Supply 20A
  • Pasaban MC-2006 03 CAN Bus PLC Card
  • ETAS ES600.2 PLC Module Prototyping
  • ABB ACS800-01-0005-3+P901 Frequency Converter
  • Omron NX102-1100 PLC Module Machine Automation
  • Square D BMXCPS3500 PLC Power Supply Module
  • Allen-Bradley 96657704 Fiber Optic Converter 1771-AF
  • Corcom 20VK1 Power Line Filter
  • Novellus 2805-11407 PLC Rack Assembly
  • Sick RLY3-EMSS100 Safety Relay Module
  • Microchip PIC12F508-I/P Microcontroller
  • Fanuc A02B-0098-B511 Motherboard
  • Merlin Gerin PB80 PLC Rack Module
  • ABB Pluto S20 V2 CFS Safety PLC
  • Honeywell TK-PRR021 Redundancy Module
  • B&R 7XX419L.50-1 Bus Controller
  • Mitsubishi NV400-SW 3P 300A Breaker
  • B&R X20AT2222 Temperature Module
  • Corcom 20VK1 EMI RFI Filter
  • Novellus 2805-11407 PLC Rack Assy
  • Mitsubishi FXAOM01BD Analog Output Module 4CH
  • NORIS A1-91 PCB Rack Module A1-91-4 A1-91-5 A1-91-6 A1-91-7 A1-91-8
  • Omron ZFV-SC50 Smart Camera Vision Sensor
  • Schneider Electric EOCR-PMZ Motor Protection Relay
  • B&R X20 SO 6300 PLC Module Safety Output
  • Mitsubishi A2ACPU21-S1 CPU Module MELSEC
  • Siemens 6ES7405-0KA02-0AA0 PS405 10A Power Supply
  • Samsung PVU-2424 Power Supply Unit DC24V 24W
  • ATTO controlSYS ATT0-CPU44 PLC with Display
  • Lenze EPZ-10203 CANPT010W3E Absolute Encoder
  • GE IS215WEMAH1A+IS210BPPBH2CAA Mark VIe Embedded Processor and Backplane Power Distribution Board
  • GE IS215AEPAH1CH+IS210BPPBH2CAA Mark VIe Application Processor and Backplane Power Distribution Board
  • GE IS215WECAH1B+IS210BPPBH2CAA Mark VIe Control Platform
  • GE PCM Regulator for EX2100e Power Conversion Module 151X1235DB15SA1
  • Lenze ECSEA048C4B servo drive