ABB Electrical 1SAM101901R0001 HK-11 Auxiliary Contact Module 1NO+1NC
Basic Information
Model No.: 1SAM101901R0001, the product ID corresponds to the product name HK-11.
Product type: It belongs to the control products in low-voltage products and systems, specifically the auxiliary contact module of manual motor starter.
Technical Parameters
Rated working voltage: AC 400V, DC 250V.
Rated working current: 3A at 24V, 3A at 120V, 2A at 240V, 0.5A at 380/400V under AC-15 conditions; 2.5A at 24V, 0.55A at 125V, 0.27A at 250V under DC-13 conditions.
Rated Frequency: 50Hz or 60Hz and DC for auxiliary circuits.
Rated surge withstand voltage: 6kV for auxiliary circuits.
Rated insulation voltage: 690V.
Protection rating: IP20.
Dimensions and Weight
Dimensions: Net width 9mm, net height 86mm, net depth/length 72mm.
Net weight: 0.03kg.
Connection and torque
Terminal block type: Screw terminals.
Auxiliary circuit connection capacity: 1/2x0.75...1.5mm cross-section of flexible conductor. . 1.5 mm², flexible conductors with insulating jacket 1x0.75.... .2.5 mm², flexible conductor with insulation sleeve 2x0.75 mm², flexible conductor 1/2x0.75.... .1mm², rigid conductor 1/2x1.0.... .2.5mm².
Tightening torque: 0.8...1.0N・m for auxiliary circuits. .1.0N・m.
Scope of application
Suitable products: For manual motor starters MS325, MO325, etc.
Temperature range: Operating temperature range - 25°C to + 50°C, storage temperature range - 50°C to + 80°C.
Approvals and Standards
The product complies with many international standards, such as IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1, etc., and has been awarded CQC certificate, CUL certificate, CE marking, UKCA marking, UL certificate and so on.
The AC 800F is available in two versions:
• 4 MB static RAM, 4 MB EPROM
• 16 MB synchronous dynamic RAM, 8 MB EPROM
The AC 800F optionally provides several levels of redundancy:
• device redundancy with 2 AC 800F
• power supply redundancy (24 V DC)
• Ethernet communication redundancy (standard)
• Cable redundancy for Profibus DP, requires external equipment (RLM01)
AC 800F Controller Redundancy
Controller redundancy can be achieved by installing two AC 800F. To ensure quick and smooth takeover by the secondary AC 800F in case the primary AC 800F fails, a dedicated redundancy communications link through the second Ethernet module makes sure that both AC 800F are always synchronized. All inputs and outputs are designed to support redundant operation.
email:1583694102@qq.com