Product Description:
The safety-related F35 controller is a compact system located in a metal enclosure with 24 digital inputs, 8 digital outputs, 2 counters and 8 analog inputs.
The controller is available in 3 model variants for SILworX and 3 model variants for ELOP II Factory.
The device is suitable for mounting in Ex-zone 2, see Chapter 4.1.5. The device has been certified by the TÜV for safety-related applications up to SIL 3 (IEC 61508, IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1).
The controller is equipped with safety-related digital inputs and outputs, safety-related counters and safety-related analog inputs.
The controller is equipped with 24 digital inputs. The state (HIGH, LOW) of each input is signaled by an individual LED.
The input signals are captured as analog measurements and provided to the program as a range of INT values from 0...3000 (0...30 V). Configurable thresholds are used to generate BOOL values
The default setting is:
Low level: < 7 V
High level: > 13 V